H3C S12500X-2L Quick Start Manual Download Page 22

 

3-12 

2. 

Use screws to attach the DC input terminal block to the rack. 

Figure 3-14 Attaching a DC input terminal block to a rack 

 

 

To connect power wires to a DC input terminal block: 

1. 

As shown by callout 1 i

Figure 3-15

insert the wires of the extension cable into the upper-row 

terminals on the DC input terminal block, and insert the other ends of the wires into the 
terminals on the power distribution cabinet. 

2. 

As shown by callout 2 i

Figure 3-15

, insert the wires of the DC power cord into the lower-row 

terminals on the DC input terminal block, and insert the other ends of the wires into the 
terminal block on the switch. 

Figure 3-15 Connecting wires to a DC input terminal block 

 

 

(Optional) Installing transceiver modules 

 

CAUTION: 

  To prevent particles from entering the ports, install the dust plugs that come with the interface 

modules in the QSFP+/QSFP28 ports if you are not to install transceiver modules or cables in 
the ports. 

 

1RU

Flat-head screwdriver

RTN

NEG

RTN

NEG

1

2

Summary of Contents for S12500X-2L

Page 1: ...H3C S12500X 2L Switch Quick Start Guide New H3C Technologies Co Ltd http www h3c com Document version 5PW101 20200722...

Page 2: ...espective owners Notice The information in this document is subject to change without notice All contents in this document including statements information and recommendations are believed to be accur...

Page 3: ...face module 3 3 Removing an interface module 3 4 Installing a filler panel in an empty interface module slot 3 5 Installing cable management brackets 3 5 Installing and removing fan trays 3 6 Installi...

Page 4: ...The switch must be used indoors To ensure correct operation of the switch and to prolong its service lifetime the installation site must meet the load bearing temperature humidity cleanliness EMI gro...

Page 5: ...79 in from the rack facing surface of the mounting brackets to the power supply handles at the chassis rear A minimum of 1 1 m 3 61 ft in depth recommended A minimum of 130 mm 5 12 in from the front r...

Page 6: ...nstallation positions are at the same height on the four rack posts 3 Install cage nuts in the marked square holes on each rack post except for the uppermost marked square holes on the front rack post...

Page 7: ...g mounting brackets Before mounting the chassis in the rack install cage nuts on the front rack posts for attaching the mounting brackets by performing the following steps 1 As shown in Figure 2 3 det...

Page 8: ...he rack 1 Face the rear of the chassis towards the front of the rack 2 Move the switch by holding the chassis handles 3 Place the switch on the slide rails from the front of the rack and slide the swi...

Page 9: ...grounding cable to the grounding strip 1 Unpack the grounding cable The grounding cable provided with the switch is compliant with the NEBS standards The two hole grounding lug of the grounding cable...

Page 10: ...cting the grounding cable to a grounding strip 1 Grounding sign 2 Use grounding screws to attach the two hole grounding lug to the grounding point 3 Grounding strip 4 Grounding post 5 Ring terminal 6...

Page 11: ...ee Figure 1 1 for attaching an ESD wrist strap Installing and removing SEUs CAUTION If you are not to install an SEU in an SEU slot keep the filler panel in the slot When you install an SEU avoid dama...

Page 12: ...old the ejector lever to pull the SEU part way out of the slot See callout 2 in Figure 3 2 3 Holding the SEU by the front panel with one hand and supporting the bottom with the other pull the SEU stea...

Page 13: ...tective blank panel 1 Remove the screws that secure the protective blank panel to the switch See callout 1 in Figure 3 3 2 As shown by callout 2 in Figure 3 3 remove the protective blank panel with bo...

Page 14: ...n by callout 4 in Figure 3 4 push the ejector levers inward until they come in close contact with the panel 7 As shown by callout 5 in Figure 3 4 fasten the captive screws to secure the interface modu...

Page 15: ...t 2 in Figure 3 6 fasten the captive screws on the filler panel The recommended torque is 5 kgf cm 0 49 Nm Figure 3 6 Installing the filler panel in an empty interface module slot Installing cable man...

Page 16: ...at the LED is on the right side of the front panel To avoid damaging the fan tray use both hands when installing or removing a fan tray When you hot swap a fan tray only one fan tray is operating and...

Page 17: ...own by callout 1 in Figure 3 9 loosen the captive screws on the fan tray 2 Squeezing the captive screw at the air vents side with one hand and holding the fan tray handle pull the fan tray outward unt...

Page 18: ...ler panel and pull out the filler panel along the guide rails See callout 1 in Figure 3 10 2 Correctly orient the power supply If you install the power supply in a left power supply slot make sure the...

Page 19: ...nd pull the power supply out of the slot slowly See callout 2 in Figure 3 11 Figure 3 11 Removing a power supply Connecting the power cord CAUTION Power on the switch after you have completed installa...

Page 20: ...r over the wiring terminals and use a Phillips screwdriver to remove the M5 screws The recommended torque is 20 kgf cm 1 96 Nm 2 Connect the wire marked with the negative polarity symbol to the negati...

Page 21: ...he power distribution cabinet Terminals on the power distribution cabinet do not support customization A DC input terminal block provides eight pairs of terminals Each pair has the blue terminal for r...

Page 22: ...distribution cabinet 2 As shown by callout 2 in Figure 3 15 insert the wires of the DC power cord into the lower row terminals on the DC input terminal block and insert the other ends of the wires in...

Page 23: ...odule up Holding the module gently push the module into the slot until it has firm contact with the slot as shown in Figure 3 16 For a module that uses a plastic pull latch skip this step If you canno...

Page 24: ...s take consideration of the layout of the equipment room including the locations of the power distribution cabinet AC power receptacles and lightning protection box Place all re connecting facilities...

Page 25: ...DB 9 female connector of the console cable to the serial port of the PC 2 Plug the RJ 45 connector of the console cable to the console port of the switch Figure 5 1 Connecting a terminal to the consol...

Page 26: ...Ware Version 1 02 Copyright c 2004 2019 New H3C Technologies Co Ltd Compiled Date Jul 4 2019 Memory Type DDR4 SDRAM Memory Size 16384MB Memory Speed 2133MHz flash Size 7296MB CPLD 1 Version 0 0 CPLD 2...

Page 27: ...llowing items The cooling system is working and you can hear fan rotating noise and feel air being blown out The LEDs on the SEUs show that the system is operating correctly For more information about...

Reviews: