Chapter 3  Installation

 

3-5 

Connect the ground screw to the grounding bar using a PGND cable. It is required 

that a grounding resistance should be less than 5 ohm. If you install the SecPath in a 

19-inch standard rack, you must also ground the rack.

 

3.4  Connecting Power Cable

 

The SecPath supports: 

z

 

AC input power supply module 

z

 

DC input power supply module 

You can choose one from them as needed. Both of them are the same in terms of 

features and functions, except for the PWR type. 

3.4.1  Connecting AC Power Cable

 

I. AC Input Power Supply

 

AC power input range: 90 to 264V AC, 50/60Hz.

 

Figure 3-5

 shows AC input power socket. 

 

1. Cable-retention clip 

2. AC input 

3. Power switch 

 

Figure 3-5 

Partial appearance of AC power socket

 

II. Recommended AC Power Socket

 

You should use a 3-line single-phase power socket with a grounding terminal, which 

should be reliably connected to the ground in the building.  

Normally, the grounding terminal of the power supply system in a building was buried 

in the ground during the construction and cabling. You must make sure that the power 

Summary of Contents for H3C SecPath F1800-A

Page 1: ...2 3 2 1 Mounting a SecPath into the Rack 3 2 3 2 2 Mounting a SecPath onto the Workbench 3 3 3 3 Connecting the PGND 3 4 3 4 Connecting Power Cable 3 5 3 4 1 Connecting AC Power Cable 3 5 3 4 2 Connec...

Page 2: ...the equipment to the specified location Connect the PGND wire Connect the power cord Connect the equipment to the console terminal Install interface module Connect the equipment to the Ethernet Connec...

Page 3: ...the 19 inch standard rack Its dimensions are 436 2 mm Width 420 mm Depth 130 5 mm Height Its weight is 20 kg with full configuration Follow the steps below to mount a SecPath Step 1 Make confirmation...

Page 4: ...he shelf or guides 3 Push it into the rack Step 4 Fix the equipment to the rack Fix the equipment to the rack with M3 screw through brackets as shown in Figure 3 3 1 2 3 4 5 1 rack 2 Mounting brackets...

Page 5: ...en installing and using the SecPath otherwise the SecPath and the peer equipment may be damaged The SecPath provides a separate PGND screw You must properly connect the PGND to the ground In this way...

Page 6: ...hem are the same in terms of features and functions except for the PWR type 3 4 1 Connecting AC Power Cable I AC Input Power Supply AC power input range 90 to 264V AC 50 60Hz Figure 3 5 shows AC input...

Page 7: ...cket on the rear panel and fix the cable onto the cable retention clip with a cable strap Connect the other end of the cable to the AC power socket Step 3 Place the power switch to the ON position Ste...

Page 8: ...not make mistakes Step 3 Place the power switch to the ON position Step 4 Check that the POWER LED on the front panel is ON which means the power cable is correctly connected 3 5 Connecting the Consol...

Page 9: ...console terminal The console terminal can be z Standard ASCII terminal fit with an RS 232 serial port z Regular PC The latter is often used Step 2 Connect the cable 1 Power off the SecPath and the co...

Page 10: ...45 connectors at both ends are the same It is used to connect a terminal device such as PC and the SecPath to a hub or LAN switch The cables delivered with the equipment are straight through cables z...

Page 11: ...e fixed LAN interface of the SecPath Step 3 If the network cable is a straight through cable connect the other end of it to the Ethernet interface of a hub or a LAN switch 3 7 Connecting the SecPath t...

Page 12: ...ble refer to Appendix A III Connecting the AUX Cable Follow steps below to connect the AUX cable Step 1 Insert the RJ 45 connector of the AUX cable into the AUX interface of the SecPath Step 2 Insert...

Page 13: ...here is enough space around the cabinet for heat dissipation z The cabinet is stable enough z The correct power supply is used z The PGND wire of the SecPath is connected properly z The connections wi...

Reviews: