H2O BOILER
HC SERIES IOM Manual
Table 5: Vent Termination Guide Line
Canadian installation (note 1)
US installation (note 2)
A =
Clearance above grade,
veranda, porch, deck, or
balcony
12 in (30 cm)
12 in (30 cm) (Note 7)
B =
Clearance to window or door
that may opened
6 in (15 cm) for appliances ≤ 10,000
Btuh (3 kW), 12 in (30 cm) for
appliances > 10,000 Btuh (3 kW) and ≤
100,000 Btuh (30 kW), 36 in (91 cm)
for appliances > 100,000 Btuh (30 kW)
4 ft (1.2 m) below or to
side of opening; 1 ft
(300 mm) above
opening
C =
Clearance to permanently
close window
See note 4
See note 4
D =
Vertical clearance to
ventilated soffit located
above the terminal within a
horizontal distance of 2 ft
(61 cm) from the center line
of the terminal
See note 4
See note 4
E =
Clearance to unventilated
soffit
See note 4
See note 4
F =
clearance to outside corner
See note 4
See note 4
G =
Clearance to inside corner
See note 4
See note 4
H =
Clearance to each side of
center line extended above
meter/ regulator assembly
See note 4
See note 4
I =
Clearance to service
regulator vent outlet
Above a regulator within 3 ft (91 cm)
horizontally of the vertical center line
of the regulator vent outlet to a
maximum vertical distance of 15 ft
(4.5 m)
See note 4
J =
Clearance to non-mechanical
air supply inlet to building or
the combustion air inlet to
any other appliance
6 in (15 cm) for appliances ≤ 10,000
Btuh (3 kW), 12 in (30 cm) for
appliances > 10,000 Btuh (3 kW) and ≤
100,000 Btuh (30 kW), 36 in (91 cm)
for appliances > 100,000 Btuh (30 kW)
4 ft (1.2 m) below or to
side of opening; 1 ft
(300 mm) above
opening
K =
Clearance to a mechanical
air supply inlet
6 ft (1.83 m)
3 ft (91 cm) above if
within 10 ft (3 m)
horizontally
L =
clearance above paved
sidewalk or paved driveway
located on public property
7 ft (2.13) See note 5
7 ft (2.13 m)
M =
Clearance under veranda,
porch, deck, or balcony
12 in (30 cm) See note 6
See note 4
Notes:
1.
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2.
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
3.
For clearances not specified in ANSI Z223.1/ NFPA 54 or CSA-B149.1. Clearance in accordance with local installation
codes and the requirements of the gas supplier
4.
“Clearance in accordance with local installation codes and the requirements of the gas supplier.”
5.
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
dwellings and serves both dwellings.
6.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
7.
Value is the minimum from the average snow line, refer to local codes for more specific requirements.