SETTING THE TIME AND DAY OF THE WEEK

With the thermostat on, press the button        . The Hour digits will blink. Use 

the + and - buttons to set the time.
Press the button          again to move to the minutes and use the + and - 

buttons to set the minutes.
Finally press the button             again and the day of the week will flash, with 

the number 1 representing Monday, 5 representing Friday, 6 representing 

Saturday and 7 representing Sunday.

»

TOGGLE BETWEEN MANUAL AND AUTOMATIC MODE

With the thermostat on, press the button        quickly to switch between 

manual and automatic mode. In manual mode you will see the symbol         on 

the display and in automatic mode you will see the programming that is 

active (                                 ).

»

SET TEMPERATURE IN MANUAL MODE

With the thermostat turned on in manual mode, use the + and - buttons to set 

the temperature.
The thermostat turns on when the temperature of the probe is lower than the 

one set at 1.5ºC and the symbol        appears on the screen. This symbol means 

that the cable or network is heating up. The thermostat switches off when the 

probe temperature is higher than the one set at 1ºC.

»

DAILY AND WEEKLY SCHEDULE

This thermostat supports 6 daily and 3 weekly programs (6 programs from 

Monday to Friday and two programs for Saturday and Sunday, or 6 programs 

from Monday to Saturday and two for Sunday or 6 programs from Monday to 

Sunday).

Press the button          for 5 seconds and you will see the days of the week (          

 

       ), use the + and - buttons to select the type of programming you 

desire:
-                        : 6 programs for the week plus 2 programs for the weekend
-                             :  6 programs from Mon. to Saturday plus 2 programs for Sunday
-                                     : 6 programs from Monday to Sunday.

Press the button          again quickly and you will have the temperature of the 

first weekly program (    ) flashing, use the + and - buttons to set the tempera-

ture.
If you want to change the start time of the program press the button         and 

you will see the hour digits flashing, use the + and - buttons to set the time. 

Press the button       again and the minute digits will flash, use the + and - 

buttons to set the program start minutes. Press the button         again to return 

to the temperature.
Press the button         quickly to go to the next program and repeat the process 

until all the programs are defined.
NOTE 1: Daily schedules are sequential, so if the first program has been 

programmed to start at 10:00 , the second cannot start at 09:00.
NOTE 2: There is no opening and closing of the daily programming period. If 

you do not want heating for some time, you must set a temperature low 

enough so that the thermostat does not start.
NOTE 3: During programming, if you do not press any button for 15 seconds, 

you will exit programming mode.
NOTE 4: When the thermostat is operating in automatic mode, you can 

manually change the temperature set for that daily period using the + and - 

buttons. The symbol              will flash. Changes made manually while in 

automatic mode are canceled when is started a new daily period.

»

CHILD LOCK

With the thermostat on, press the button        for 5 seconds to lock / unlock the 

thermostat.

Period

Icon

Default Time

Default Temperature

Week

Weekend

1
2
3
4
5
6
1
2

06:00
08:00
11:30
12:30
17:30
22:00
08:00
23:00

20 ºC
15 ºC
15 ºC
15 ºC
22 ºC
15 ºC
22 ºC
15 ºC

VIII - ADVANCED SETTINGS

With the thermostat turned off, keep the button - pressed and press the 

button         to enter the advanced settings menu. Press the button         to 

move to the next settings.

»

SEN - PROBE SELECTION

This configuration allows you to choose which probe or probes to use, with 00 

being the ambient probe, 01 the floor probe and 02 both probes. The factory 

setting is 00. Use the + and - buttons to define the probe to be used.
If option 02 is set (both probes in use), the thermostat display in normal 

operation shows only the temperature of the ambient probe. To check the 

temperature of the floor probe, keep the button           pressed and simultane-

ously press the button        .

»

OSV - FLOOR PROBE LIMIT TEMPERATURE

This function allows you to configure the temperature limit of the floor probe.
This value defines a safety temperature, from which the thermostat switches 

off, regardless of its programming.
This setting only takes effect if both probes are being used.
Use the + and - buttons to set the value that can range from 5ºC to 99ºC. The 

factory set value is 42ºC.

»

DIF - TEMPERATURE DIFFERENTIAL ASSOCIATED WITH THE LIMIT OF THE

FLOOR PROBE

This function allows you to configure the temperature differential associated 

with the limit of the floor probe. For example, if you have set a value of 2ºC in 

this option and set 40ºC in the previous function, the thermostat will switch 

off at 42ºC and switch on again at 38ºC. Use the + and - buttons to set the 

value that can range from 1ºC to 9ºC. The factory set value is 2ºC.

»

SVH - HIGH TEMPERATURE LIMIT FOR ROOM TEMPERATURE 

This function allows you to configure the high temperature limit of the 

ambient probe. The thermostat switches off when the ambient probe reaches 

this temperature. Use the + and - buttons to set the value that can range from 

5ºC to 99ºC. The factory-set value is 35ºC.

»

SVL - LOW TEMPERATURE LIMIT FOR ROOM TEMPERATURE 

This function allows you to configure the low temperature limit of the 

ambient probe. The thermostat switches off when the ambient probe reaches 

this temperature. Use the + and - buttons to set the value that can range from 

5ºC to 99ºC. The factory set value is 5ºC.

»

ADJ - CORRECTION OF THE AMBIENT PROBE TEMPERATURE

This function allows to correct the temperature of the ambient probe. This 

correction is applied when the temperature displayed by the room probe is 

not equal to the actual room temperature (measured with another external 

device). This can happen due to the installation or position of the thermostat. 

Use the + and - buttons to set the value. The factory-set value is 0ºC.

»

FRE - ANTI-FROZEN

This function allows to activate or deactivate the anti-frozen function. With 

this function active, the thermostat starts automatically when the tempera-

ture of the ambient probe is below the low temperature limit defined in the 

SVL function. A value of 0 means that the function is off and a value of 1 

means that the function is on. The factory setting is 0.

»

PON - MEMORY FUNCTION IN CASE OF POWER FAILURE

This function allows you to define whether or not the thermostat should 

memorize its settings in the event of a power failure. A value of 0 means that 

the function is off and a value of 1 means that the function is on. The factory 

setting is 0.

»

FAC - DEFINIÇÕES DE FÁBRICA

This function allows you to reset all settings and functions to the factory 

values. Use the + and - buttons to set the value. 00 will reset all values   to 

factory defaults. If you do not want to make changes, select the value 08.

Erro

Cause

Solution

ERR

Floor probe error

Replace floor probe

IX - ERROR TABLE