background image

 

D1130 

- Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-8 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed 
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance 
with condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault leds condition as well as output to be correct. 

Power Dissipation of D1130 Isolators

 

Section “Technical Data” of D1130 isolator specifies the current consumption (maximum current from the nominal power supply); this data serves to dimension the current rating of the 
power supply unit. Section “Technical Data” indicates also the maximum power consumption (maximum power required from the power supply in the worst (abnormal) operating 
conditions like, short circuit on the outputs and on the inputs terminals. 
The power dissipated 

Pd

 inside the enclosure for analog signal isolators is: 

Pd = Current Consumption (A) * Supply Voltage (V) - Power Dissipated into the input/output loads 

Digital signal isolators have lower dissipation than analog signal isolators, in addition 2 channels barriers (D1130D) have higher dissipation than single channel units (D1130S). 
Isolators are not running at the maximum current all at the same time, the average power consumption of a multitude of isolators can be considered to be only 70 % of the value obtained 
from the section “Technical Data”. Considering the 1/3 load power and the 70 % above discussed, the power effectively dissipated internally by the isolators can therefore become ½ of 
the actual power delivered by the power supply. Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet, with mixed 
analog and digital barriers, is determined by the number of channels more than by the number of isolator enclosures. The following tables give advises for the DIN rail orientation 
(vertical or horizontal) of the barriers mounting, D1130D (double channel) and D1130S (single channel) isolators, installed on DIN rail or custom board assembly. 

A) 

Cabinet with Natural Ventilation 

Maximum recommended ambient temperature in °C depending on barrier type and installation method: 

 

Installation in Cabinet 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-rail Bus 

Single unit Installation 

 

Type of Isolator 

 

 

 

Vertical 

Horizontal 

Installation on Custom Boards 

B) 

Cabinet with Forced Ventilation 

Maximum recommended ambient temperature in °C depending on barrier type and installation method: 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-rail Bus 

Single unit Installation 

 

Type of Isolator 

 

60°C 

40°C 

45°C 

Vertical 

Horizontal 

Installation on Custom Boards 

45°C 

50°C 

 

 

D1130S 

60°C 

30°C 

35°C 

D1130S 

60°C 

Not recommended 

(1)

 

30°C 

D1130D 

35°C 

40°C 

30°C 

35°C 

(1)

 Installation is not recommended since it would significantly shorten the units life and increase the probability of failures. 

60°C 

40°C 

45°C 

45°C 

50°C 

D1130D 

 

Installation 

 

D1130 series are AC supply switch/proximity detector repeaters housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
D1130 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches. 
Identify the number of channels of the specific card (e.g. D1130S is a single channel model and D1130D is a dual channel model), the function and location of each connection terminal 
using the wiring diagram on the corresponding section, as an example: 
Connect AC power supply (85 to 250 Vac, 48 to 400 Hz) at terminal “3” and “4” (limit supply voltage to Um 250 Vrms for Intrinsic Safety applications). 
For Model D1130S connect common relay contact output of channel 1 at terminal “1”, normally closed contact at terminal “8” and normally opened contact at terminal “2”. 
For Model D1130D connect common relay contact output of channel 2 at terminal “5”, normally closed contact at terminal “7” and normally opened contact at terminal “6”. 
For Model D1130S connect proximity sensor or voltage free contact at terminal “13” for positive and “14” for negative. 
For Model D1130D in addition to channel 1 connections above, connect terminal “15” for positive and “16” for negative on channel 2. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
Connect SPDT relay contacts checking the load rating to be within the contact maximum rating (2 A, 250 V, 500 VA 80 W resistive load). 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1130 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1130 series must be connected to supply non exceeding category II, pollution degree II overvoltage limits. 
Relay output contact must be connected to loads non exceeding category II, pollution degree II overvoltage limits. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential

Summary of Contents for D1130D

Page 1: ...D1130 Switch Proximity Detector Repeater Relay Output ISM0048 8 D1130S D1130D INSTRUCTION MANUAL INSTRUCTION MANUAL Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Page 2: ...channels D1130D 1 9 W for 1 channel D1130S Isolation Test Voltage I S In Out 2 5 KV I S In Supply 2 5 KV Out Supply 2 5 KV Out Out 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with si...

Page 3: ...ut for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High Density two channels per unit Simplified installation using stan...

Page 4: ... Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A Co...

Page 5: ...pparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB C IIA D IIC A B Lo La 172 mH Lo La 689 mH Lo La 1379 mH IIB C IIA D IIC A B Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to G...

Page 6: ...NE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free Cont...

Page 7: ...ult condition of sensor and connecting line are displayed by signaling LEDs green for power yellow for status and red for fault condition D1130D dual channel type has two independent input channels and actuates the corresponding output relay SPDT contact two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally energized relay or Normally cl...

Page 8: ...50022 D1130 unit can be mounted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detailed instructions Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powe...

Page 9: ...tection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON 1 OFF 4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND...

Page 10: ...led proximity sensor or contact with terminating line resistor Out B Out A 1 2 8 5 6 7 Out A 1 2 8 Out B 5 6 7 No Fault 5 6 7 5 6 7 NE NE NE ND ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resisto...

Reviews: