GUILCOR AR004798 User Manual Download Page 22

 22 

Float32b 

two Modbus registers containing IEEE754 float, lower 16bits first, 
error value = -inf 

Int32b*100 

two  Modbus  registers  containing  32bit  signed  integer*100, 
12.53dgrC = 1253, lower 16bits first, error value <= -320000000 

Ascii 

two ASCII character in register 

BCD 

registry is coded as BCD 

n/a 

item is not defined, should be read 

SOAP 

The device allows you to send currently measured values via 

SOAP v1.1

 protocol. The device 

sends values in  XML format to  the  web server. The advantage of  this protocol is that 

communication is initialized by the device side. Due to it is not necessary use port forwarding. 
If the  SOAP message cannot be  delivered, warning message via SNMP Trap or  Syslog 

protocol  is  sent.  The  file  with  the  XSD  schema  can  be  downloaded  from: 

www.guilcor.com.  

SOAP message example: 

Host: 192.168.1.132 
Content-Type: text/xml; charset=utf-8 
Content-Length: 656 
SOAPAction: "http://tempuri.org/InsertP2520Sample" 

<?xml version="1.0" encoding="utf-8"?> 
<soap:Envelope xmlns:soap="http://schemas.xmlsoap.org/soap/envelope/" 
xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" 
xmlns:xsd="http://www.w3.org/2001/XMLSchema"> 

<soap:Body> 

  <InsertP2520Sample xmlns="

www.guilcor.com

<name>

Current Loop Converter

</name>

 

<sn>

11940986

</sn>

 

<tmr>

60

</tmr>

 

<kind>

4357

</kind>

 

<c1> 

<n>

Channel 1

</n>

<v>

3.25

</v>

<f>

00005040

</f>

<u>

mA

</u>

<a>

no

</a>

<p>

2

</p>

<e>

1

</e>

</c1> 

<c2> 

<n>

Channel 2

</n>

<v>

18.00

</v>

<f>

00009041

</f>

<u>

mA

</u>

<a>

no

</a>

<p>

2

</p>

<e>

0

</e>

</c2> 

</InsertP2520Sample> 

  </soap:Body> 

</soap:Envelope> 

Summary of Contents for AR004798

Page 1: ...Guilcor www guilcor com AR004798 two channel current loop converter USER GUIDE...

Page 2: ...d free repairs during the warranty period Revision history This manual describes devices with latest firmware version according to table below Older version of manual can be obtained from a technical...

Page 3: ...faults 16 Communication protocols 19 Website 19 SMTP sending e mails 19 SNMP 19 Modbus TCP 21 SOAP 22 XML and JSON 23 Syslog 24 SNTP 24 Troubleshooting 25 I forgot the device IP address 25 I cannot co...

Page 4: ...ice by the qualified service person if you think that is not working properly It is forbidden to use the device without the cover Inside the device can be a dangerous voltage and may be risk of electr...

Page 5: ...log server The device setup can be made by the web interface Latest firmware version can be obtained from the technical support Do not upload to your device firmware which is not designed for it Unsup...

Page 6: ...ree IP address in your network sensor s with current loop output 4 20 mA or 0 20 mA Mounting the device check if the equipment from the previous chapter is available install the latest version of TSen...

Page 7: ...according to image below Inputs channels on the device are not galvanically isolated Power supply is not isolated from inputs as well Device is isolated from communication line side only Carefully co...

Page 8: ...ed if you want to use the device in local network only If you set the same IP address which is already used the device will not work correctly due to IP address collision If the device detects a colli...

Page 9: ...web interface Web interface can be managed by the web browser Main page will be shown when you insert device address into address bar of your web browser There you find actual measured values Page wi...

Page 10: ...btained automatically from DHCP server using option Obtain an IP address automatically Static IP address is configurable via field IP address It is not necessary setup Default gateway while is device...

Page 11: ...was not set In Point 3 the value has risen over limit again During the time delay the value does not drop below the set limit and therefore was in Point 4 caused alarm At this moment were sent e mails...

Page 12: ...col SOAP protocol can be enabled by option SOAP protocol enabled Address of the destination http server is configurable via SOAP server address filed For setup of destination server port can be used o...

Page 13: ...cipient 1 to Recipient 3 it is possible set address of email recipients Option Short email enable sending emails in short format This format is usable when you need to forward emails into SMS messages...

Page 14: ...ort field Syslog protocol can be enabled using item Syslog enabled Syslog messages are sent to IP address of the Syslog server field Syslog server IP address SNMP For reading values via SNMP it is nec...

Page 15: ...every hour decreases this synchronization interval to one hour WWW and security Device security features can be enabled by the Security enabled option When security is enabled it is necessary to set...

Page 16: ...to be restored all device settings with exception network settings www and security settings Factory defaults Factory defaults button set the device into factory configuration Network parameters IP a...

Page 17: ...password cleared Modbus port 502 Modbus server enabled yes History storage interval sec 60 SOAP server address cleared SOAP server port 80 SOAP sending interval sec 60 Send SOAP message when alarm occ...

Page 18: ...18 Number of decimal places 2 Device name Current Loop Converter...

Page 19: ...ce Reboot of the device is performed when the power supply is disconnected and after some configuration changes SMTP sending e mails When measured values are over the set limits the device allows send...

Page 20: ...1 4 1 22626 1 6 2 ch 10 0 Actual current mA String 1 3 6 1 4 1 22626 1 6 2 ch 11 0 Actual current uA 120uA 120 Integer 1 3 6 1 4 1 22626 1 6 2 ch 12 0 Alarm on channel 0 1 2 Integer 1 3 6 1 4 1 22626...

Page 21: ...4 0x9C26 Device type Int16b 39975 39976 0x9C27 0x9C28 Current on channel uA Int16b 39977 39978 39979 39980 0x9C29 0x9C2A 0x9C2B 0x9C2C Actual value channel1 Actual value channel2 Float32b 39981 39982...

Page 22: ...If the SOAP message cannot be delivered warning message via SNMP Trap or Syslog protocol is sent The file with the XSD schema can be downloaded from www guilcor com SOAP message example Host 192 168...

Page 23: ...0 err devname My device devname devsn 13940001 devsn time 2021 04 06T07 48 44 01 00 time timeunix 1617695324 timeunix synch 1 synch ch1 name Humidity name unit RH unit aval 34 93 aval alarm 1 alarm ch...

Page 24: ...file not found SOAP message sending error SOAP dns error SOAP host error SOAP sock error SOAP delivery error High alarm CHx Upper alarm on channel Low alarm CHx Lower alarm on channel Clearing CHx Cl...

Page 25: ...address Follow the software instructions To assign IP address automatically using DHCP server set the device IP address to 0 0 0 0 Device IP address is not displayed in window Find device In TSensor s...

Page 26: ...ocumented error Please contact technical support Error 5 Internal Error CRC Please contact technical support Error 6 Current is under low limit Please contact technical support Error 7 Current is over...

Page 27: ...upply voltage DC voltage from 9 V to 30 V Consumption 1 W device without powering connected sensors Protection IP30 Measuring interval 1 sec faster readings is available via ModbusTCP protocol for mor...

Page 28: ...mmended Connector Cable for industrial use there is recommended Cat5e STP cable in less demanding applications can be replaced by Cat5 cable maximum cable length 100 m Supported protocols TCP IP UDP I...

Page 29: ...End of operation Disconnect the device and dispose it according to current legislation for dealing with electronic waste Electronic devices must be professionally destroyed Technical support and serv...

Reviews: