49
Expert Net Control 2302
© 2021 GUDE Systems GmbH
Configuration
actual temperature
during configuration
actions
70 °C
Port 1 Off (above max) + Port 2 On (above min)
45 °C
Port 1 On (below max) + Port 2 On (above min)
20 °C
Port 1 On (below max) + Port 2 Off (below min)
Action matrix during operation when limit values are exceeded (for given example):
to "above max" to "below max" to "above min" to "below min"
from "above
max"
-
P1 On
P1 On
P1 On + P2 Off
from "below max"
P1 Off
-
-
P2 Off
from "above min"
P1 Off
-
-
P2 Off
from "below min" P1 Off + P2 On
P2 On
P2 On
-
Only the switching operations for which actions have been defined, are triggered. If
no "On" or "Off" action is defined for a port, the port can never reach this state by ex-
ceeding sensor values. Unless it is the initial state.
3.7
Enable E-Mail: Activates the E-Mail dispatch of messages.
Sender address: The E-Mail address of the sender.
Recipient address: The E-Mail address of the recipient. Additional E-Mail addresses,
separated by comma, can be specified. The input limit is 100 characters.
SMTP Server: The SMTP IP-address of the E-Mail server. Either as FQDN, e.g:
"mail.gmx.net", or as IP-address, e.g: "213.165.64.20". If required, attach a designated
port, e.g: "mail.gmx.net:25".
SMTP server port: The port address of the E-Mail server. In the normal case this
Summary of Contents for Expert Net Control 2302