Figure 1-8. – Connection for 120 Volts Only
RECONNECTION FOR DUAL VOLTAGE OUTPUT:
When connected for dual voltage output, Stator out-
put leads 11P and 44 form two “hot” leads (T1- Red
and T3- Black). The junction of leads 22P and 33
form the “Neutral” line (T2- White).
For dual voltage output, the “Neutral” line remains
grounded.
NOTE: For units with two 30 amp or two 35 amp
main breakers, the existing breakers may be re-
used when reconnecting for dual voltage output.
However, on units with a 30 amp and a 20 amp
main breaker, you may wish to install a 2-pole
breaker that is rated closer to the unit’s rated
capacity (use two 25 amp main breakers).
Figure 1-9 - Connection for 120/240 Volts
NOTE: If this generator has been reconnected for
dual voltage AC output (120/240 volts), the
replacement line breakers should consist of two
separate breakers with a connecting piece
between the breaker handles (so that both break-
ers operate at the same time). If the unit is recon-
nected for dual voltage, it is no longer RVIA listed.