                                                                                                  Issue 2.03

 

                                       

 

 

Features 

  Electronically addressed. Address can be modified 

in field. 

  Built-in  microprocessor  processes  information     

intelligently.   

  Reusable button can be reset manually. 

  Providing an independent output contact. 

  Plug-in structure.   

Description 

I-9201 Intelligent Manual Call Point (MCP) is installed 
in  public  places.  When  there  is  a  fire,  pressing  the 
nearest  MCP,  alarm  signal  can  be  sent  to  the  fire 
alarm  control  panel  (FACP).  And  the  FACP  will  show 
the address of the MCP, and give alarm sound. 

The  MCP  is  operated  by  pressing  the  mechanically 
latched button to reduce possibility of accidental alarm. 
The  built-in  microprocessor  can  execute  alarm 
checking  and  communication  with  the  control  panel. 
The  microprocessor  contains  an  EEPROM  to  store 
messages like address and device type.     

Connection and Cabling 

Fig.1 shows terminals of the MCP. 

Conduit

Mounting 
Hole

65mm

 

Fig.1

 

Connection:   

Z1, Z2: Loop connection, polarity-insensitive.     

K1, K2: Volt-free normally open contact. 

Recommended Cabling:   

1.0  mm

or  above  fire  cable  for  Z1,  Z2.  1.5  mm

or 

above fire cable for K1, K2. Subject to local codes. 

 

 

 

 

 

 

Installation 

Unplug  the  MCP,  thread  the  cable  through  the  wiring 
hole of the base box and connect it to corresponding 
terminals,  and  plug  the  MCP  back.  The  base  of  the 
MCP  can  be  surface  mounted  or  flush  mounted  as 
shown in Fig.2 and 3. 

B-9311 Back Box

Conduit

Back Box

MCP

Conduit

MCP

                  Fig.2                                      Fig.3

 

Warning: Before installing the MCP, disconnect the 
power  from  the  loop  and  verify  that  all  bases  are 
securely  installed  and  that  the  wiring  polarity  is 
correct at each base. 

Application 

Connect the terminals Z1 and Z2 to the loop of control 
panel directly. 
(1) Before operation, the MCP should be programmed 

by  P-9910B  Hand  Held  Programmer.  Please  refer 
to  P-9910B  Hand  Held  Programmer  Installation 
and Operation Manual for details. 

(2) If the connection and wiring are correct, the control 

panel should be able to register the MCP. 

(3) When fire occurs, pressing the glass on the MCP, 

the LED should flash quickly and the control panel 
should display fire alarm message. 

(4) Please  reset  the  MCP  in  time  when  fire  alarm  is 

disposed. 

The Intelligent Solution 

I-9201 

Intelligent Manual Call Point

 

 