34
The
GTO, Inc. Technical Service Department
is open
Monday – Friday 8:00
A.M.
– 5:00
P.M.
(Eastern Time)
Fax (850) 575-8950 • Web site: www.mightymule.com
E-Mail: [email protected]
Telephone (800) 543-1236
Telephone (850) 575-4144
VOLTAGE RATINGS
If the Opener is Working
18 Vac Transformer ___________________________
18 Vac Transformer
18 Vac Transformer
18.0 to 22.0 Vac
5 W Solar panel (single) _______________________18.0 to 22.0 Vdc 300 mA
measure voltage at panel and control box.
12 V Battery ________________________________12.0 to 13.5 Vdc 7.0 Ah
Charging circuit _____________________________12.0 to 14.8 Vdc
measure voltage with battery connected
The Gate CLOSES Then Opens Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary.
2. Check the gate for binding or hinge damage.
The Gate OPENS Then Closes Again on its Own:
1. Check the position of the mounting brackets and readjust if necessary.
2. Check the gate for binding or hinge damage.