GST303 /GST306
Extinguishing Control Panel
Installation and Operation Manual
Page 13
Table 1
Position of S1
0
1
2
3
4
5
6
7
8
9
Corresponding
initial address
1
21
41
61
81
101
121
141
161
181
After the initial address is set, the addresses of control enable pin, emergency start
button, emergency stop button, gas extinguishment and addresses reserved for future
use
will be automatically set in sequence according to the number of zone control
board. No matter how many zones are configured to the control panel (1 ~ 6), control
enable pin (alarming action when disabled) occupies an address, which is the initial
address. Each zone occupies four addresses:
(1) Emergency Start Button (action).
(2) Emergency Stop Button (action).
(3) Gas extinguishment (pressure switch action and local fault).
(4) Reserved for future use.
The number of addresses occupied by the control panel = n x 4 + 1 (n is the maximum
quantity of zones, 1~6).
For example, in Fig. 5-5, S1 is set as 0, then the initial address is 1, in other words, the
number of the control enable lock is 1. The addresses of other points are shown in
Table 2.
Table 2
Zone Number
Address Zone Number
Address
Zone
No. 1
Emergency Start Button
2
Zone
No. 4
Emergency Start Button
14
Emergency Stop Button
3
Emergency Stop Button
15
Gas extinguishment
4
Gas extinguishment
16
Reserved
5
Reserved
17
Zone
No. 2
Emergency Start Button
6
Zone
No. 5
Emergency Start Button
18
Emergency Stop Button
7
Emergency Stop Button
19
Gas extinguishment
8
Gas extinguishment
20
Reserved
9
Reserved
21
Zone
No. 3
Emergency Start Button
10
Zone
No. 6
Emergency Start Button
22
Emergency Stop Button
11
Emergency Stop Button
23
Gas extinguishment
12
Gas extinguishment
24
Reserved
13
Reserved
25
5.6.3 Setting Delay Time
Because extinguishing device will finish gas release instantaneously on receiving valid
start command, improper operation will result in great losses, even loss of life; On the
other hand, it will affect the fire protective ability of some important places in a certain
period. For these reasons, the control panel is designed with delay started feature.
When receiving start request, it will delay for a certain time, and give command when
delay ended. To meet requirements under different conditions, the delay time can be
set by code switch S2 on the main board (see Fig. 5-6) within 0s
~
45s.