background image

♦ 

Microprocessor based controller 

♦ 

16 detector zones 

♦ 

Maximum 25 detectors in each zone 

♦ 

Day / night mode  

♦ 

Short / open circuit detection   

♦ 

Compact size 

♦ 

Easy programming

 

CONVENTIONAL FIRE ALARM  PANEL

 

GST116 

FEATURES 

DESCRIPTION 

GST116 Conventional Fire Alarm Control Panel is a microprocessor based multi-zone fire alarm 
control panel which is fully complied with European Standard EN54-2. The configuration of the 
system is programmable and saved in non-volatile memory that will remain the program on the 
panel even when the panel lost both the main power and battery power. 

The panel has 16 detector zones. Each zone can be connected with up to 25 GST smoke or heat 
detectors while using end of line resistor; or 15 smoke detectors or heat detectors with the active 
end of line unit. The manual call points can be wired in the same detector zone with the smoke 
detectors or heat detectors. The number of the manual call points is unlimited. 

The panel has five supervisory outputs and one 
non-supervisory output. They are four supervi-
sory sounders and one supervisory alarm output 
and one non-supervisory fault output (N.O. and 
N.C. contact).  

The panel has functions of alarm indication, 
fault indication, testing mode and isolation 
mode, Day / Night Mode selection.  

The operation of the panel is simple. All control 
functions and programming are made by the 
keypad and switches on the panel or the 
switches and jumpers on the circuit board. No 
other programming tools are required.  Two 
keys are provided to ensure secured operation 
of the control panel.  

This model provides a simple and low-cost 
solution to protect a small space from fire 
such as houses, shops, hotels, schools and 
factories. 

Number of  detector zone

 

16

 

Number of sounder output 

 

4

 

Power supply

 

187~242Vac

 

Operating temperature

 

0°C to  40°C

 

Detector loop voltage

 

24

±4Vdc

 

 

Max. number of detectors per 
loop with end of line resistor 

25 

Max. number of detectors per 
loop with active end of line unit 

15 

Detector impedance  
for fire alarming 

 

150

 ~ 1.5k

  

(normally 470

)

 

End line resister of  
detector loop

 

4.7k

 

Sounder output voltage

 

24

±4Vdc

 

 

Max. output current

 

1A

 

End line resister of sounder 
output

 

4.7k

 

Auxiliary power  output

 

24Vdc, 0.5A

 

Standby battery

 

7Ah

 

Dimension

 

380 x 320 x 95mm

 

SPECIFICATION 

 

 

GST116 