GST GST-RP16 Installation And Operation Manual Download Page 4

 

 

GST-RP16 Conventional Repeater Panel

 

                       

 

 

                

Installation and Operation Manual

     

                                          

       

 

Page 2 

2.    Front panel is shown in Fig. 2. 

Fig. 2 

Instructions of Key and Indicators: 

 

Power ON

This green LED is constantly lit after the power is on. 

 

FIRE

General fire alarm light. 

a red LED, lit when there is a fire signal. 

 

ZONE1~ZONE16

Zone  fire  lights,  red  LEDs,  lit  if  there  are  fire  alarms  in 

corresponding zones. The flashing of an LED indicates it is the latest fire alarm. 

 

FAULT

Fault light, yellow, lit when there is a fault signal. 

 

MUTE

 Pressing this key in alarm or fault state can silence the alarm sound, while 

it gives another sound to indicate the mute state. 

3.    Operation Principle 

GST-RP16 is a zonal fire display panel developed with microprocessor. It indicates 
the alarm zone with LED and audio-visual signal. It connects with conventional 
FACP  with  multi-wire,  providing  alarm  signal  after  processing  the  data  from 
conventional FACP. 

V  Mounting and Commission 

1.  Mounting 

GST-RP16 is wall-mounted. Drill two 5 holes on the wall as shown in Fig. 3, push 
two 5 plastic expansion sleeves into the holes, then fix the back of GST-RP16 
with expansion bolts and connect wires.  

 

 
 
 
 
 
 

Fig. 3 
 
 

ZONE12

MUTE

ZONE14

ZONE16

ZONE 2

ZONE 4

ZONE 6

ZONE 8

ZONE10

PowerON

ZONE11

ZONE 1

ZONE 3

ZONE 5

ZONE 7

ZONE 9

FAULT

FIRE

ZONE13

ZONE15

Summary of Contents for GST-RP16

Page 1: ...GST RP16 Conventional Repeater Panel Installation and Operation Manual Issue 1 03 Jan 2014 ...

Page 2: ...er Panel Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 1 V Mounting and Commission 2 VI Operations 3 VII Troubleshooting 3 VIII Cautions 4 ...

Page 3: ...es separately 2 With two fault outputs it can show fault signals from conventional FACP 3 It is wall mounted with advantages of small dimension simple installation and operation good performance high reliability and flexible configuration etc III Technical Specifications 1 Display Capacity Maximum 16 signals 2 fault signals 2 Wiring Connect with conventional FACP by multi wire 16 for fire signals ...

Page 4: ... state can silence the alarm sound while it gives another sound to indicate the mute state 3 Operation Principle GST RP16 is a zonal fire display panel developed with microprocessor It indicates the alarm zone with LED and audio visual signal It connects with conventional FACP with multi wire providing alarm signal after processing the data from conventional FACP V Mounting and Commission 1 Mounti...

Page 5: ... The buzzer alarms fire After self test Power ON LED is lit other LEDs are off and the buzzer doesn t sound 4 Keep chassis well grounded to ensure stable operation VI Operations 1 Put the jumper X1 ON 2 In monitoring state only Power ON LED is lit 3 When there is a fire alarm the FIRE LED is lit and the zonal FIRE LED corresponding to conventional FACP is also lit If it is the latest fire relevant...

Page 6: ... in input part b Insulated optocoupler does not work c Output circuit is damaged d Transistor oscillator or main CPU damaged a Connect it in a right way b Replace the optocoupler c Check 74HC595 and ULN2003 d Check transistor oscillator or replace main CPU 4 No sound a Output circuit is damaged b Buzzer is damaged a Check 74HC595 and ULN2003 b Replace the buzzer VIII Cautions 1 Before powering up ...

Reviews: