Page 5
4.2
Networked Fire Telephone System
The system consists of a group of panels as many as 8. The panel with the address 1 is the
main panel and the rests are sub-panels. Please refer to commission section for setting up
addresses.
Fig. 4-2
5 Mounting & Commission
5.1
Initial Check
Check the appearance of the panel after open the box. Then power on and check working
state.
5.2
Wiring Requirement
Cross-section area of the power cable not less than 1.5mm
2
Twisted-pair cable connecting panel and handset with SA not less than 1.0 mm
2
Twisted-pair cable for the network with SA not less than 1.0 mm2
The cable selection must comply with local code