![GST GST-FT40N Installation And Operation Manual Download Page 7](http://html1.mh-extra.com/html/gst/gst-ft40n/gst-ft40n_installation-and-operation-manual_2275577007.webp)
GST-FT40N
Fire Telephone Panel
The Intelligent Solution
Page 5
Fig. 4-2
5 Mounting & Commission
5.1 Initial
Check
Check the appearance of the panel after open the box. Then power on and check working
state.
5.2 Wiring
Requirement
¾
Cross-section area of the power cable not less than 1.5mm
2
¾
Twisted-pair cable connecting panel and handset with SA not less than 1.0 mm
2
¾
Twisted-pair cable for the network with SA not less than 1.0 mm
2
¾
The cable selection must comply with local code
Note: the impedance of single line not more than 20
Ω
5.3 Installing
dimension
Installing dimension
:
482.5mm*177mm*225mm