30312268                                                                                                                                                                          Issue 1.06

 

Testing 

Note:  Before  testing,  make  sure  the  detector  is 
properly  installed  and  powered  up.    Testing  can 
only begin after the detector is powered up for 10 
seconds.   

The  detector  must  be  tested  after  installation  and 
regular maintenance. The methods are as follows: 

(1) Reed switch testing 

The testing area of the detector is shown in Fig. 4.   

Approach  the  commission  tool  to  the  testing  area  of 
the  detector  and  hold  for  several  seconds  until  the 
detector alarms. 
(2) Temperature test 
Approach  a  heater  (such  as  a  hair  drier)  to  the 
thermistor of the detector until it alarms. 

Testing 
Area

Fig. 4

 

(3) After testing, disconnect the power to the detector 

for  over  5  seconds  to  reset  it.  Notify  the  proper 
authorities  that  the  system  is  back  to  normal 
operation. 

(4) If a detector fails in testing, clean it by the steps in 

“Maintenance”, and retest it. If it still fails, return it 
for repair. 

Maintenance 

1. The  detector  should  be  installed  just  before 

commission and kept well before installation, taken 
corresponding measures for dust-proof, damp-proof 
and corrosion-proof. 

2. The  dust  cover  should  not  be  removed  until  the 

project  has  been  plunged  into  usage.  Otherwise  it 
may not report alarm normally. 

3. The detector should be cleaned at least every year 

to ensure normal operation of the system. 

4. Before  cleaning,  notify  the  proper  authorities  that 

the  system  is  under  maintenance  and  will 
temporarily be out of service. Disable the automatic 
controls  relating  to  the  zone  or  system  under 
maintenance to avoid unwanted actions. 

5. The  detector  should  be  tested  after  cleaned  and 

re-installed to ensure normal operation.

 

6. Protect  the  conductive  metal  element  on  the 

detector base from humidity or rigid distortion.

 

7. Fire simulation test should be  done to the detector 

at least every 6 months.

 

Accessories and Tools 

Model 

Name 

Remarks 

P-9910B 

Hand Held 
Programmer 

Order separately 

DB-01 

Base 

Order separately 

T-MT 

Commission Tool 

Order separately 

 
 
 
 

 

Specification 

WEEE Information 

2012/19/EU  (WEEE  directive):  Products 
marked  with  this  symbol  cannot  be 
disposed of as unsorted municipal waste in 
the European Union. For proper recycling, 
return  this  product  to  your  local  supplier 

upon  the  purchase  of  equivalent  new  equipment,  or 
dispose of it at designated collection points. 

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  of  charge 

for  repairing  or  replacing  from  defects  in  design, 
materials and workmanship during the warranty period. 
This warranty does not cover any product that is found 
to have been improperly installed or used in any way 
not  in  accordance  with  the  instructions  supplied  with 
the 

product. 

Anybody, 

including 

the 

agents, 

distributors  or  employees,  is  not  in  the  position  to 
amend  the  contents  of  this  warranty.  Please  contact 
your  local distributor for products  not  covered  by this 
warranty. 

Operating Voltage 

Loop 24V(16V

28V)       

Standby Current 

≤0.6mA   

Alarm Current 

≤1.5mA (without remote indicator) 
≤3.5mA (with remote indicator) 

Indicator 

Red,  Flashes  in  polling,  and 
illuminates in alarm 

Remote indicator 
output 

Polarity-sensitive, 

directly 

connects to remote indicator (built 
in 10k resistor in series. Maximum 
output current is 2.0mA);   
The  remote  indicator  is  quiet  in 
normal and flashing in alarm.   

Programming 
Method 

Electronically programmed 

Code Range 

One address within 1~242. 

Classes and 
Setup   

3classes 

(A1R, 

A2S, 

BS) 

programmable 

Wiring 

Non-polarized 2-core for loop. 
Polarized 2-core for remote 
indicator. 

Ingress Protection 
Rating 

IP2X 

Ambient 
Temperature 

Class A1: -10

~+50

 

Class A2: -10

~+50

 

Class B: -10

~+65

 

Typical Fixed 
Temperature 

Class A1:    58

 

Class A2:    62

 

Class B:      77

 

Relative Humidity 

95%, non-condensing 

Material   

ABS 

Dimensions 

Diameter: 100mm 
Height: 53.3mm (with base) 

Mounting Hole 
Distance 

45mm~75mm 

Weight 

About 110g (with base) 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 