background image

 

30312268                                                                                                                                                                          Issue 1.06

 

 

   

Features 

 

Electronically addressed in field. 

 

3 classes programmable.   

 

Self-diagnostic. 

 

Reed switch testing. 

 

Fire LED allows 360

°

viewing. 

 

Remote indicator output available. 

 

Designed to comply with EN 54-5 standard. 

 

Polling LED can be set to close. 

Description 

DI-9103E  Intelligent  Rate  of  Rise  and  Fixed 
Temperature Heat  Detector is  a new addressable fire 
alarm  device  cooperating  with  GST  intelligent  fire 
alarm  control  panels(FACP)  to  build  a  fire  detection 
system.  The  detector  shows  fire  alarm  by  the  LED 
indicator and transmits the signal to the FACP.   

Connection and Wiring 

Fig.1  shows  the  detector  bottom  and  Fig.  2  DB-01 
base.   

C

B

A

 

Fig. 1                                Fig. 2 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 

2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 

Recommended Wiring 

1.0mm

2

 or above fire cable for all terminals laid through 

metal conduit or flame retardant conduit but subject to 
local codes.   

Note: It

’s recommended to use cables of different 

colors to avoid incorrect wiring. 

Installation 

A fixed installation direction is ensured by the location 
elements  on  the  detector  and the  base.  Fix  the  base 
with two tapping screws, and then align mark A on the 
detector  with  B  on  the  base,  rotate  the  detector  to 
align mark A with mark C (Refer to Fig. 1 and 2 for the 
position of the marks), the detector will be fitted to the 
base. 

 

 

 

Fig. 3 shows the schematic for mounting the detector.

  

Detector

Base

Conduit

Electric box

53.3mm

 

Fig. 3 

Application 

The  detector is  especially applicable  to places  where 
fire  occurs  with  sharp  rise  of  temperature.  Used 
together  with  smoke  detectors,  it  can  detect  fire  with 
more reliability to reduce losses. 
The  detector  can  be  addressed  in  field  by  using 
P-9910B programmer. Please refer to 

P-9910B Hand 

Held  Programmer  Installation  and  Operation  Manual 

for details. 
The default class of the detector is A1R, which can be 
modified using the programmer.   
When  the  programmer  is  in  standby  state,  entering 
unlock  password  and  pressing  “Clear”,  it  will  be 
unlocked.  Pressing 

Function

  followed  by 

4

, there  will 

be  a  “-”  at  the  last  digit.  Entering  different  number 
corresponding to the classes ( 

“2” for A1R, “3” for A2S) 

followed  by 

“Program”,  there  will  be  a  “P”  shown  on 

the  screen,  indicating  the  class  is  programmed. 
Pressing 

“Clear”  can  clear  the  “P”,  and  entering 

locking password followed by 

“Clear” will exit.   

Table 1 Detector setting parameters 

Input Number 

Class 

Polling LED State 

A1R 

Normal 

A2S 

Normal 

BS 

Normal 

130 

A1R 

Close 

131 

A2S 

Close 

133 

BS 

Close 

Read Heat Detector Class: 

When the programmer is 

in standby state, pressing 

Test”, it will display address 

of the detector. Pressing 

“Up”

, it will display sensitivity 

level, device type and heat detector class in turn. 

DI-9103E Intelligent Rate of Rise   

and Fixed Temperature Heat Detector

 

548c/04 

2831-CPR-F0006 

GST-0005-01 

              14 

Reviews: