background image

HTTP://WWW.HOMBI.RU

 

30304559                                                 

                               

 Issue 2.01

 

   

Features 

—

 

Electronically addressed in field.   

—

 

Built-in microprocessor stores 14 history data. 

—

 

Rate of rise temperature mode is optional. 

—

 Variable 

alarm 

points. 

—

 

Identification of defective detectors. 

—

 

The fire LED allows 360° viewing. 

—

 

Providing output terminal connecting with remote 
indicator. 

—

 

Standard: EN 54-5. 

Description 

DI-9103 Digital Dual Heat Detector is a new 
generation product, connected with intelligent fire 
alarm control panel to form fire alarm system. The 
detector turns on fire LED to indicate fire alarm 
condition and transmits the fire signal to the control 
panel.

 

With P-9910B programmer, the detector can be set at 
rate of rise or fixed temperature mode, it has three 
alarm points when it is in latter mode.

  

Wring and Connection 

The orientation base DB-01 is shown in Fig. 2

.

 

A

C

B

 

Fig. 1                                          Fig. 2 

Connection: Detector loop should be connected with 
terminals “1” and “3” of the base, polarity-insensitive; 
terminals “2” to anode of the remote indicator and “4” 
to the cathode. 

Recommended Wiring 

1.0mm

or above fire cable for detector loop, laid out 

through metal conduit or flame-resistant conduit, 
subject to local codes. The connection of remote 
indicator should use different color cables to distinct 
polarity.  

Installation 

Fix the base with two taping screws. Then align A 
(Fig.1) on the bottom of the detector to B (Fig. 2) of the 
base, and rotate the detector clockwise to mark C.   

Mounting of the detector is shown in Fig. 4.

 

 

 

 

 

 

Mounting of the detector is shown in Fig. 3. 

Detector

Base

Conduit

Electrical Box

47.8mm

 

Fig. 3 

 

Application 

The detector is especially applicable to places where 
fire occurs with highly rise of temperature. Used 
together with smoke detectors, it can detect fire with 
more reliability to reduce losses.

 

Electrically addressed, the detector is easy to be 
programmed by P-9910B Programmer in field. Refer 
to P-9910B Hand Held Programmer Installation and 
Operation Manual for details.

  

Device type of the detector is defaulted rate of rise 
temperature, which can be changed into fixed 
temperature through hand held programmer. 

In the 

power-on state of the programmer, input an unlocking 
password and press 

Clear

 to unlock the programmer. 

Press 

Function

, then number 4, the screen will display 

“—“ at last digit. Input the parameter, press 

Program

the screen will display “P” meaning the relevant 
parameter has been written in. Press 

Clear

 to remove 

that. Input locking password, then press 

Clear

 to 

return. Enter number 4 to set the detector as fixed 
temperature, and 2 as rate of rise temperature. 

When the detector sets at fixed temperature, it has 
three sensitivities. In power on state of the 
programmer, input an unlocking password and press 

Clear

 to unlock the programmer. Press 

Function

, then 

number 3, the screen will display “—“ at last digit. 
Input the related sensitivity (1, 2, 3 for sensitivity I, II, 
III individually), press 

Program

, the screen will display 

“P” meaning the related sensitivity level has been 
written in. Press 

Clear

 to remove that. Input locking 

password, then press 

Clear

 to return. 

Maintenance 

1. The detector should be installed just before 

DI-9103 

Digital Dual Heat Detector   

The Intelligent Solution 

HTTP://GSTRU.RU

E-MAIL: [email protected]