background image

 

30309533

               

                                                                                                     

       

  Issue 1.04

 

                                       

 

Features 

 

Strong  environmental  adaptability  due  to  drift 
compensation. 

 

Self-diagnostic. 

 

Reed switch testing.   

 

Removable  innovative  sensing  chamber,  easy  for             
maintenance. 

 

Dirty chamber checking. 

 

 

Fire LED allows 360

°

viewing 

  Remote indicator output available.   

  Polling LED can be set to close. 

 

2 levels smoke sensitivities  programmable, level 1 
complies with EN 54-7. Heat part complies with EN 
54-5. 

Description 

DI-9101E  Intelligent  Combination

 

Heat  Photoelectric 

Smoke  Detector  integrates  photoelectric  detection  and 
fixed  temperature  and  rate  of rise  detection  technology 
by  combining  smoke  sensor  and  semi-conductor  heat 
sensor  in  mechanism  and  circuitry  structure.  Just 
because of the combination of smoke detection and heat 
detection,  it  not  only  overcomes  the  disadvantage  that 
detectors  using  common  infrared  scattering  technology 
are  insensitive  to  black  smoke  with  small  particles,  but 
also  can  pick  up  fire  with  obvious  rise  of  temperature 
such  as  alcohol  flame,  thus  extending  its  application 
range. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 DB-01 base. 

C

B

A

                   

Fig. 1                              Fig. 2 

There are four terminals with numbers on the base.   

1&3: Loop connection (polarity-insensitive) 
2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator 

Recommended Cabling 

1.0mm

2

  or  above  fire  cable  is  recommended,  laid 

through metal or flame-retardant  conduit,  but  subject  to 
local  codes.  Different  color  cables  for  remote  indicator 
are used to avoid wiring mistake. 

Installation 

A  fixed  installation  direction  is  ensured  by  the  location 
elements on the detector and the base. Fix the base with 
two  tapping  screws,  and  then  align  mark  A  on  the 
detector with B on the base, rotate the detector to align 
mark A with mark C (Refer to Fig. 1 and 2 for the position 
of the marks), the detector will be fitted to the base. 
 
 
 

 

Fig. 3 shows the installation of the detector. 

51.5mm

Electrical Box

Conduit

Base

Detector

 

 

Fig. 3 

Application

 

The detector can be addressed in field by using P-9910B 
programmer.  Please  refer  to 

P-9910B  Hand  Held 

Programmer  Installation  and  Operation  Manual

  for 

details. 
In  power-on  state,  input  unlocking  password  and  press 

Clear

  to  unlock.  Press 

Function

,  then  press  “3”,  the 

screen shows “-” at the last digit.   
Input  corresponding  sensitivity  or  parameter  and  press 

Program

, the screen will show a “P”, the corresponding 

sensitivity  or  parameter  is  programmed.  Press 

Clear

  to 

clear the "P". Input locking password and press 

Clear

 to 

return. 
Rate of rise and level 1 is defaulted.   

Parameters set using programmer 

Input 

Parameter 

of a Detector 

Smoke 
Sensitivity 

Heat Part 

Polling LED 

Rate of Rise 

Normal 

Rate of Rise 

Normal 

129 

Rate of Rise 

Close 

130 

Rate of Rise 

Close 

Read Sensitivity Level: in power-on state, pressing 

Test

the  screen  displays  address  of  the  detector.  Pressing 

Up”,

  display  sensitivity  level,  device  type  and  initial 

sensitivity in turns.   

Testing 

Before  testing,  please  ensure  that  the  detector  has 
been  installed  correctly  and  powered  up.  After  10 
seconds, testing begins.

 

1) The  detector  must  be  tested  after  installation  and 

periodical maintenance. 

2) Testing method 

a) 

Reed Switch Testing 

Magnetic  test  zone  is  shown  in  Fig.  4.  Put  the 
magnet  of  commission  tool  close  to  that  of  the 
detector  and  hold  on  for  a  few  seconds  until  the 
detector generates alarm. 

DI-9101E Intelligent Combination

 

 

Heat Photoelectric Smoke Detector

 

0832-CPR-F0339 

GST-0507-01 

              14 

             

           

   

 