background image

 

30310469                                                                                                                                                      Issue 1.04 

                                       

 

Features 

 

Isolation of short circuit, automatic restore when 
short circuit is cleared. 

 

Maximum output current is 1A. 

 

DIN-Rail mounted or Wall mounted. 

 

Standard: EN 54-17:2005 

Description   

In fire alarm system, such condition often occurs that 
partial  short  circuit  of  loop  affects  the  whole  system. 
DC-9503E Loop Isolator

hereinafter referred to as the 

isolator

can isolate the shorted circuit from the whole 

system  to  ensure  normal  operation  of  other  devices 
and  help  locate  the  devices  in  fault.  After  the  short 
circuit  fault  is  cleared,  those  devices  will  be 
re-introduced into the system. 

The  isolator  is  suitable  for  use  in  the  loop  of 
addressable fire alarm system. 

Connection & Cabling 

Terminals of the isolator are shown in Fig. 1. 

 

Fig.1 

(I+, I-) IN & OUT: input signal loop, I+ is positive and I- 
is negative.   
O+,  O-:  output  signal  loop,  O+  is  positive  and  O-  is 
negative.   
Recommended Wiring:  1.0mm

or  above twisted  pair. 

Wires  should  not  be  laid  out  in  the  same  conduit  or 
raceway  with  Class  1  wires  such  as  power  cables, 
high and low voltage distribution cables and so on. 

 

 

 

 

 

 

Installation 

1) 

Before installation, make sure the enclosure is in 
good condition and markings are complete. 

2) 

The  isolator  can  be  mounted  on  a  35mm 
DIN-Rail as shown on Fig. 2.   

3) 

The  isolator  can  also  be  wall  mounted  by  4 
mounting  screws  as  shown  in  Fig.  3.  Mounting 
space is 67mm. 

 

Fig. 2 

 

Fig. 3 

Application 

System connection is shown in Fig. 4. Note: Terminals 
of the isolator have polarities.     

 

2831-CPR-F2019 

GST-0017-01 

 

18 

548n/05 

DC-9503E 

  Loop Isolator   

 