background image

 

30306463                                                                                                                                                                       

   

Issue 2.04

 

 

 

 

Features 

 

High sound level. 

 

Circuitry and base are twisted together. 

 

Standard: EN 54-3. 

Description 

C-9404 Conventional Sounder is a kind of audible alarm 
device  used to  warn  people in field  when fire  occurs. It 
can  give  audible  alarm  when  applied  to  24VDC  power 
(D1  connected  with  anode  and  D2  with  cathode).  To 
connect it  with fire  alarm control  panel,  an  addressable 
control module should be added to the system, such as 
I-9301 Addressable Single I/O Module. 

Both shallow base with 25.5mm high and deep base with 
40mm high are available, deep base is used if there is no 
special statement in this manual.

 

Connection and Wiring 

Terminals on the base are shown in Fig. 2. 

G

1

K

1

D

D

2

1

2

Z

2

K

S

Z

97.5mm

80mm

55mm

Arch knock off Hole

5mm

       

Fig. 1                                      Fig. 2

 

D1 (9), D2 (7): To 24VDC power, polarity insensitive. D1 
to anode and D2 to cathode.   

Recommended Wiring 

1.5mm

2

  or  above  fire  cable  for  24VDC  power  line, 

subject to local codes.   

Installation 

 

When  the  sounder  is  inside  the  wall,  it  can  be 

mounted on the electrical box, using a shallow base or a 
deep  base. When  the  sounder  is  on  the  surface  of  the 
wall,  it  should  be  mounted  on  the  locations  where  it  is 
0.2m from the ceiling, using a deep base only. Knock the 
knock-off  hole  (Fig.  1),  then  connect  with  the  cable 
conduit. When using a deep base, refer to Fig. 2 for hole 
spacing  and  direction,  and  Fig.  3a  and  Fig.  4  for  its 
mounting  method.  When  using  a  shallow  base,  the 
sounder has to be mounted in the wall, shown in Fig.3b. 

 

The  base  and  the  sounder  are  twisted  together. 

When  mounting,  remove  the  sounder,  thread  cables 
through  the  cable  entry  in  the  base  and  connect  with 
corresponding terminals, then twist the sounder onto the 
base. 
 

 

 

If  the  sounder  is  required  anti-removal,  knock 

down the arch knock-off hole as shown in Fig. 1 and fix it 
with ST2.9

×

6.5 tapping screws (in this case, it must be 

removed by special tools). 

Sounder 

Knock-off Hole

Conduit

Electrical Box

 

Fig. 3a 

Sounder

Conduit

Electrical Box

 

                              Fig. 3b 

       

Conduit

Sounder

 

Fig. 4 

C-9404 

  Conventional Sounder

 

 

 

Reviews: