I-9401 Addressable Sounder Strobe

 

C-9401 Sounder Strobe

                                

               

                

Installation and Operation Manual  

  

                                                

    

 

 

Page 1  

General  

Sounder Strobe is a kind of optical and visual alarm device used to warn people in field 

when fire occurs.  

GST  produces  two  types  of  sounder  strobe,  addressable  (I-9401)  and  conventional 

(C-9401). Addressable sounder strobe can be started directly by fire alarm controller.  It 

can be electronically programmed and modified by P-9910 Hand Held Programmer in 

field.  Conventional sounder strobe can give optical and visual alarm when powered by 

DC24V, and can be connected to fire alarm controller through an addressable linkage 

control module. When it is not started, wire checking can be done by loading reverse 

voltage and connecting terminal resistor at the end of the circuit. 

II  Features 

1.  Red plexiglass panel, several strong red LED as light source, striking, long-life and 

low consumption. 

2.  Fire alarm sound over 85dB, easy to catch attention. 

3.  Circuit  part  and  base  box  are  plugged  together,  reliable  contact  convenient  for 

engineering; 

Addressable: 

4.  Peripheral  control  terminals  to  startup  the  sounder  strobe  directly  by  passive 

normally open contact (e.g. manual call point), unaffected by power-cut of signal 

bus. 

5.  Signal bus and power bus non-polarized, easy for connection. 

6.  Function of checking power-cut, sending fault information to the controller. 

7.  Electronic programming of address code that can be modified on site. 

Conventional: 

8.  DC24V  two-wire,  polarized,  easy  for  wire  checking  (connecting  terminal  resistor 

when checking, the resistance value can be deiced by connecting devices). 

III  Technical Specifications 

1.  Operating Voltage (power bus terminal only for conventional): 

Signal Bus Voltage: 24V 

 

       Range Allowed: 16V

28V; 

Power Bus Voltage: DC24V  

 

Range Allowed: DC20V

DC28V 

2.  Operating Current (power alarming current only for conventional): 

Power Standby Current

10mA;  

Power Alarming Current

160mA;  

Loop Standby Current

0.8mA;  

Loop Starting Current

6.0mA. 

3.  Flashing Frequency: 20

180 times every minute when alarming; 

4.  Alarm Voice

85dB(Due front 3m horizontal (A weighted)) 

5.  Wiring: 

Summary of Contents for C-9401

Page 1: ...I 9401 Addressable Sounder Strobe C 9401 Sounder Strobe Installation and Operation Manual Issue 3 02 August 2012...

Page 2: ...r Strobe C 9401 Sounder Strobe Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Tes...

Page 3: ...tention 3 Circuit part and base box are plugged together reliable contact convenient for engineering Addressable 4 Peripheral control terminals to startup the sounder strobe directly by passive normal...

Page 4: ...al sounder strobe use sound effect chip VM42 amplified by dynatron and transformer to vocalize the speaker 6 LEDs are controlled by timing circuit giving flashing light signal Intelligent sounder is b...

Page 5: ...d mounted on 85H50 embedded box as shown in Fig 2 Fig 2 Mounting 3 The base box of I 9401 is shown in Fig 3 please note direction when installing S1 G Z2 D1 D2 Z1 Mounting Hole Mounting Hole Fig 3 I 9...

Page 6: ...outer control contact by manual call point the sounder strobe is activated and gives audio and visual alarm Cut the close signal of the outer control contact of the sounder strobe give start command t...

Page 7: ...d power bus for intelligent sounder strobe and direct control through passive normally open contact of manual call point Conventional sounder strobe connects DC24V power in direct startup D1 is positi...

Page 8: ...Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502434 Fax 86 0 335 8502532 service gst fs utc com www gst com cn 30301519...

Reviews: