background image

 

30303451                                                                                                                                                                  Issue 4.03

 

                                       

 

 
 

Features 

  Driving 220VAC devices. 

  Providing  normally  open,  normally  closed  output 

contacts. 

  Cable checking.

 

  Insulated feedback signal from 220VAC devices.

 

  Plug-in structure. 

Description 

C-9302C Interposing Relay Module is non-addressable, 
designed to  start/stop the devices driven by heavy DC 
and  220VAC.  The  module  is  used  together  with 
fireman

’s Control Panel (FCP) featuring cable checking, 

such as GST014FCP. 

Connection and Cabling 

Fig. 1 shows terminals on the module. 

9

10

15

16

8

7

2

1

C+

C-

Mounting 
Hole

Mounting 
Hole

Mounting 
Direction

COM

N

NO

NC

AN

A1

A2

65mm

6mm

 

Fig. 1

 

C

+

,  C

-

:  Input  terminals  of  start  command  signal 

(24VDC),  connecting  with  output  control  terminal  of 
fireman

’s control panel. 

A1,  A2:  Input  terminals  of  normally  open  volt-free 
feedback  signal,  connecting  with  volt-free  feedback 
terminals of controlled device. 

AN,  N:  Voltage  feedback  input  terminals  (220VAC), 
connecting  with  voltage  feedback  terminals  of 
controlled device.   

COM,  NO,  NC:  Output  control  terminals,  volt-free 

normally open, normally closed contacts (5A, 220VAC), 

connecting  with  control  terminals  of  the  controlled 

device.

 

Recommended Cabling 

1.5mm

or above fire cable for each terminal, subject to 

local codes.   

Installation 

The  module  is  simply  plugged  onto  the  base  after 
corresponding terminals are connected.   

 

 

If  the  cable  conduit  is  inside  the  wall,  the  base  is 
installed onto the Back Box (Fig. 2). If the cable conduit 
is  on  the  surface  of  the  wall,  B-9310  Back  Box  is 
available (Fig. 3).

 

Conduit

B-9310
Back

 

Box

Conduit

Module

Module

Back

 

Box

                 

Fig. 2                                                    Fig. 3 

Note the upward arrow for mounting direction (Fig. 1). 

Applications 

1.  Fig. 4 shows  that the module controls the devices 

by volt-free input mode. . 

FCP

Device

NO 

COM

C+

C-

C1-

C1+

A1

A2

Feedback

             C-9302C 

Interposing Relay Module

Fig. 4 

2.  Fig. 5 shows that  the module controls the devices 

by voltage input mode.   

FCP

N

AN

C1+

C1-

C-

C+

            C-9302C
 Interposing Relay Module

COM

NO 

Device

Feedback

Fig. 5 

The Intelligent Solution 

C-9302C   

Interposing Relay Module 

 

 

Reviews: