GST852RPX LCD Repeater Panel
Installation and Operation Manual
The Intelligent Solution
Page 4
VI Troubleshooting
Problem Reasons Solution Remark
Connecting with a
fire alarm control
panel, the repeater
panel hasn’t been
registered after
starting.
Communication
between the
repeater panel and
the fire alarm
control panel is
abnormal.
(1) The polarization
of Communication
two-wire is
reversed.
(2) The wires are
threaded in the
same tube with
strong current
circuit.
(1) Change the
polarization of
communication
two-wire.
(2) Separate the
two wire cables
from strong current
circuit.
The LED of
repeater panel
flashes regularly
when it is normal.
VII Cautions
1. This panel is precise electronic product and must be maintained by trained
personnel
.
2. This product must be in the charge of trained personnel.
3. We take charge of repairing the repeater panel. Any problem occurs, please
contact us in time. GST won’t be responsible for any result if you repair it by self.
E-MAIL: [email protected]