GSK983Ta-H/ GSK983Ta-V Turning CNC System Connection Manual
1
Precautions
1
、
The system-matched power supply box is exclusive for GSK 983Ta. Do not
supply this power to other devices (such as bake and magnetic
valve);otherwise, serious danger may occur
!
2
、
Requirements for electrical cabinet
The electrical cabinet adopts full-enclosed structure and dustproof design. The temperature
difference between outside and inside of the cabinet should be less than 10
℃
; or, a heat-exchange
system should be installed. The ambient temperature should not exceed 45
℃
. Prevent the entry of
dust, coolant and organic solution.
3
、
Grounding
The cabinet should be protectively grounded, and the continuity should meet the requirement
GB5226.1-2002. Well grounding is the essential condition for a stable operation. The grounding
wires of different parts cannot be connected with each other in series. The grounding strip whose
thickness not less than 3mm should be installed in the cabinet, the protective grounding terminals
should be connected to grounding strip with yellow-green wires independently, and when the
grounding strip is connected with the ground, its grounding resistance should be less than 4
Ω.
Electrical
Cabinet
Grounding Strip
S
M
P
S
NC
Unit
Opera
tion
Panel
I/O
Unit
X
Axis
Drive
Unit
Z
Axis
Drive
Unit
Spindle
Drive
Unit
4
、
The system power should be supplied through isolation transformer
5
、
Wiring