background image

Chapter 10: Configuring a 4 - 20mA Zone Type

NOTE:

The span entered by the user is not the

m

but rather the ratio between the normal curve and

the correction.

Setting the Calibration Zero and Calibration Span

Setting the calibration zero and calibration span ensures accuracy in the values being monitored by the
system in the event that an input is not calibrated.

What You Should Know

The calibration zero and calibration span only need to be entered if the input calibration is incorrect.

1. In edit mode, under the

General

tab, click on the edit field beside the

Cal. Zero

button.

2. Enter the zero calibration.

3. Click on the edit field next to the

Cal. Span

button.

4. Enter the calibration span.

How it Works: Calibration Zero and Calibration Span

Calibrating the zero and span errors allow the installer to correct the output of a sensor. A sensor output is
viewed as a linear function y = mx + b

Sensors that are not calibrated can generate span or zero errors as illustrated in the figures below:

895-00677

Agri Alert 128 Touch

73

Summary of Contents for 890-00584

Page 1: ...A BRAND OF Agri Alert 128 Touch Models ALERT SYSTEM 890 00584 Installation and Configuration Manual 895 00677 Version 01 895 00677...

Page 2: ...trations photos and specifications in this manual are based on the latest information available at the time of publication The right is reserved to make changes at any time without notice 2 895 00677...

Page 3: ...le to the Serial Bus Interface 29 Chapter 4 Basic Operations 31 Acknowledging an Alert On site or on the Phone 31 Arming and Disarming Intruder Zones 31 Bypassing a Zone 32 Deleting Groups of Informat...

Page 4: ...Receiving a Phone Call When an Alert is Active 54 Receiving an E mail When an Alert is Active 54 Enabling the Siren 54 Enabling the Internal Speaker 55 Recording the Zone Audio Label 55 Resetting the...

Page 5: ...ng the Daily Minimum and Maximum 78 Choosing the Type of End of Line Resistor 78 Selecting the Type of Contact in the Dry Contact Zone 78 Activating a device in the Event of an Alert or Trouble 79 Rec...

Page 6: ...er 15 Troubleshooting 93 Appendix A List of Terminals in the Main Enclosure and Battery Enclosure 97 Appendix B Battery Wire Specifications 99 Appendix C Low Voltage Cable Specifications 101 Appendix...

Page 7: ...anagement system for agricultural applications It can handle up to 128 alarm inputs spread over several buildings Main Unit Main controller with touchscreen 8 basic zones two relays and one micro phon...

Page 8: ...ach a copy of the RMA number on the shipping label 3 Complete and include the Service Form located at the back of this manual Contact information If you experience trouble with your system or to get r...

Page 9: ...pplied by the product can be compromised Carefully read all instructions Do not use the system if it does not operate correctly The enclosures must be closed and locked before you operate the product...

Page 10: ...cts the REN is separately shown on the label If this equipment phone card model PCB402 300 00319 causes harm to the telephone network the telephone company will notify you in advance that temporary di...

Page 11: ...nts are very destructive to customer terminal equipment con nected to AC power sources This has been identified as a major nationwide problem Alarm dialing equipment Notice for Equipment Utilizing A F...

Page 12: ...tective Earth Ground Terminal Primarily used for protective earth terminals Terminal connected to conductive parts of a device for the purpose of safety and is intended to be connected to an external...

Page 13: ...e storing it for an extended period After extended periods of storage it may be necessary to charge and discharge the sealed lead acid battery several times to obtain maximum performance Keep the seal...

Page 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...

Page 15: ...ture is between 20 C and 25 C 68 F 77 F The temperature should not go lower than 0 C 32 F and should not exceed 40 C 104 F Ensure there is sufficient ventilation around the unit Install the modules fa...

Page 16: ...ches 305 mm 12 inches 305 mm 12 inches 305 mm 12 inches 305 mm 12 inches Correctly Supporting and Routing Cables Properly supporting and routing the cables helps avoid electromagnetic interferences an...

Page 17: ...f the product enclosures are not sealed correctly and the installation does not respect the manufacturer recommendations the warranty is void WARNING Ensure all cables enter through the bottom of the...

Page 18: ...installation depending on bedrock depth 00000 00000 00000 00000 00000 00000 00000 00000 0000000 0000000 0000000000 0000000000 0000000000 0000000000 000000000 000000000 3 m 10 FEET 0 6 m 2 FEET 0 6 m...

Page 19: ...Minimum length 2440 mm 8 feet Cable Specifications for Grounding The cable specifications are guidelines only Refer to your national and local regulations for compliance criteria Table 2 2 Grounding c...

Page 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...

Page 21: ...auge wire to connect the main enclosure to the battery enclosure for the battery supply You also need a twisted pair wire and shielded wire with a minimum gauge of 20 AWG for the bat tery temperature...

Page 22: ...orting structure behind the drywall mount the enclo sures onto a wooden or metal frame Do not mount the enclosures directly onto the drywall Relay Output Specifications The maximum voltage on the rela...

Page 23: ...d Customer Phone Priority Connection A customer phone priority connection is made through a regular phone outlet With this type of connection the system waits until the phone line is free before begin...

Page 24: ...me line in use the dialing equipment must be connected to a properly installed RJ31X jack The RJ31X jack must be connected in series with and ahead of all other equipment attached to the same phone li...

Page 25: ...an unswitched AC power outlet and a telephone plug IMPORTANT Mount the system into a wooden or metal frame Do not mount the system directly into the drywall 1 Using four of the eight 4 76 millimeters...

Page 26: ...t is active The use of a siren is optional Before You Begin NOTICE The maximum voltage supplied to the siren is 12 VDC with a maximum current of 1 ampere NOTICE The siren s audio must not exceed 120 d...

Page 27: ...mplete or when servicing Use the nut and bolt included or a padlock not included to lock the enclosure 1 Ensure there is no switch on the power outlet 2 Plug the wire from the power supply into a powe...

Page 28: ...block VBAT on the main board in the main enclosure 5 Connect the other end of the cable to the positive terminal BATTERY in the battery enclosure Connecting the Battery Temperature Sensor 1 Run a 20 A...

Page 29: ...ure 2 Connect the wire shielding to the terminal marked SHIELD 3 When connecting an external microphone connect the SIGNAL and CASE terminals to the microphone The auxiliary terminal marked as AUX on...

Page 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...

Page 31: ...e zone back into a normal condition When on site proceed as follows 1 Either from a module with a keypad connected to the system or on the system s user interface enter your password when prompted 2 F...

Page 32: ...Begin IMPORTANT The following steps delete the entire displayed page including information in all tabs 1 Navigate to the page where you would like to delete the information 2 Click on the garbage ico...

Page 33: ...available for viewing in status mode and others are displayed when switch ing to edit mode 1 Follow the menu path of your choice 2 Click on the pencil icon to change into edit mode All tabs containing...

Page 34: ...Chapter 4 Basic Operations NOTE When a reading is not normal the box is highlighted in red or orange when a trouble is present 34 895 00677 Agri Alert 128 Touch...

Page 35: ...ess Level Rights with the access level User The contact can acknowledge alarms and view system information Master The contact can edit certain configuration parameters and parameters for every day usa...

Page 36: ...e the group to receive a test report 4 Enter the information of week day week night and weekend start times 5 Complete the Day Night and Weekend tabs with the contacts to be alerted during each time p...

Page 37: ...have access to the latest features 1 Insert the USB stick into the USB port of the main system 2 Click on Menu System Settings Software Info to view the current software firmware and hardware informa...

Page 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...

Page 39: ...ould Know NOTE More than one page of zone tiles must be available for the screen to scroll 1 Click on Menu System Settings General settings 2 In edit mode under the General tab check the Auto scroll z...

Page 40: ...inutes Number of com errors in last 5 minutes Network error in last 5 minutes 6 To reset the statistics click on the Reset Stats button Configuring and Monitoring Ethernet Data The ethernet settings a...

Page 41: ...the correct zones the outputs can activate or deactivate equipment during an alert that could potentially save livestock Before You Begin NOTE The programmable outputs must first be configured before...

Page 42: ...ceive gain Increases the volume of voice reception Ranges between 48dBm and 9dBm and increases by increments of 3dBm Transmit gain Increases the volume of the emitting voice Ranges between 48dBm and 9...

Page 43: ...for system troubles the system waits the recognition time before going into trouble state and then waits for the system to return to a normal state for the amount of time indicated in the recovery tim...

Page 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...

Page 45: ...d circuit and some types of sensors Intrusion detection Used to detect intrusion through normally open NO or normally closed NC cir cuits This zone type cannot be assigned to a partition and cannot ha...

Page 46: ...on offset X X Output Activation on Alert or Trouble X X only trouble X X X Alert Phone Call X X X X X X Alert E mail X X X X X X Alert Texting SMS X X X X X X Alert Siren X X X X X X Internal Speaker...

Page 47: ...ng the Zone with a Text Label The zone text label is a name you give to a zone to facilitate its identification In addition to the zone number the text label appears everywhere where the zone is ident...

Page 48: ...stem and that are initialized in the system are available for selection Selecting an Input 1 In edit mode under the General tab click on the Input edit field to display the selection box 2 Select the...

Page 49: ...isplaying an example of an alert with an 8 second recognition time TEMPERATURE RECOGNITION TIME 8 SECONDS TIME SECONDS HIGH ALERT THRESHOLD INDOOR T READING LOW ALERT THRESHOLD 5 10 15 20 25 30 5 SECO...

Page 50: ...decrease over a period of days 1 In edit mode under the Limits tab click on the T curve button NOTE The temperature maturation curve is only available in temperature zones 2 If you want a temperature...

Page 51: ...old What You Should Know NOTE The temperature maturation curve must be disabled in order for the system to use the high and low temperature thresholds 1 In edit mode under the Limits tab click on the...

Page 52: ...h temperature limit An alert is set off only when the indoor temperature rises above the high tempera ture limit The Ext offset value can be modified In addition there is a critical temperature settin...

Page 53: ...8 6 Graph combining the temperature maturation curve and the outdoor temperature compensation features TEMPERATURE TIME HOURS ALERT 3 HIGH ALERT THRESHOLD SET OFF B Y THE HIGH TEMP SETTING HIGH TEMPE...

Page 54: ...n calling Receiving an E mail When an Alert is Active When an alert is present in a zone the system sends the assigned contact group an e mail to inform them of the situation Receiving an e mail when...

Page 55: ...consistency use the same words as you used when giving the Name in the zone s General tab 2 State the zone audio label clearly NOTE The recording stops when it has reached the allowed time of 8 second...

Page 56: ...on tab click on the edit field next to the Offset button to display the keypad 2 Enter the impedance offset in ohms 3 Enter the temperature offset and the low and high trouble impedances NOTE Enter va...

Page 57: ...he Zone with a Text Label The zone text label is a name you give to a zone to facilitate its identification In addition to the zone number the text label appears everywhere where the zone is identifie...

Page 58: ...ystem and that are initialized in the system are available for selection Selecting an Input 1 In edit mode under the General tab click on the Input edit field to display the selection box 2 Select the...

Page 59: ...me before an alert is recognized and set off 1 In edit mode under the General tab of the zone you are configuring click on the edit field next to the Recognition button 2 Set the alert recognition tim...

Page 60: ...play according to the input connected to the zone Entering the Minimum and Maximum Values for an Input 1 In edit mode under the General tab click in the edit field next to the Min button 2 Enter the m...

Page 61: ...ent in a zone the system sends the assigned contact group an e mail to inform them of the situation Receiving an e mail when an alert is activated allows you to be alerted even when you are on the pho...

Page 62: ...the allowed time of 8 seconds 3 Click on the play icon to listen to the recording 4 If the recording is not satisfactory press the garbage icon to delete the recording and start over 5 Repeat steps 2...

Page 63: ...calibrated What You Should Know The calibration zero and calibration span only need to be entered if the input calibration is incorrect 1 In edit mode under the General tab click on the edit field bes...

Page 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...

Page 65: ...specific to the sensor output For example if you want a reading with a range of 0 to 250 PSI you can adjust the span so that when the sensor reads 250 PSI the input of the system indicates 20 mA With...

Page 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...

Page 67: ...an Viewing Zone Calibration Naming the Zone with a Text Label The zone text label is a name you give to a zone to facilitate its identification In addition to the zone number the text label appears ev...

Page 68: ...box 2 Select a module from the list NOTE Only the modules that are connected to the system and that are initialized in the system are available for selection Selecting an Input 1 In edit mode under t...

Page 69: ...Set the alert recognition time Figure 10 2 Graph displaying an example of an alert with an 8 second recognition time TEMPERATURE RECOGNITION TIME 8 SECONDS TIME SECONDS HIGH ALERT THRESHOLD INDOOR T R...

Page 70: ...the values are reset and the monitoring starts anew In status mode under the General tab in the zone you are configuring click on the Reset min max The information beside the Max 24h and Min 24h butto...

Page 71: ...he edit field next to the telephone icon 2 Click in the box to the left the contact person or group you would like to be notified in the event of an alert in the given zone After You Finish Make sure...

Page 72: ...ency use the same words as you used when giving the Name in the zone s General tab 2 State the zone audio label clearly NOTE The recording stops when it has reached the allowed time of 8 seconds 3 Cli...

Page 73: ...libration span only need to be entered if the input calibration is incorrect 1 In edit mode under the General tab click on the edit field beside the Cal Zero button 2 Enter the zero calibration 3 Clic...

Page 74: ...250 PSI the input of the system indicates 20 mA With a 0 000016 mA by PSI to get 16 mA at 250 PSI the span must be 4 By adjusting the readings you are playing with the gain and offset to have reading...

Page 75: ...ddition to the zone number the text label appears everywhere where the zone is identified in writing on the user interface 1 In edit mode under the General tab of the zone you are configuring click on...

Page 76: ...Selecting an Input 1 In edit mode under the General tab click on the Input edit field to display the selection box 2 Select the input from the list Selecting a Zone Type Selecting a zone type allows...

Page 77: ...displaying an example of an alert with an 8 second recognition time TEMPERATURE RECOGNITION TIME 8 SECONDS TIME SECONDS HIGH ALERT THRESHOLD INDOOR T READING LOW ALERT THRESHOLD 5 10 15 20 25 30 5 SEC...

Page 78: ...m and maximum values is displayed After 24 hours the values are reset and the monitoring starts anew In status mode under the General tab in the zone you are configuring click on the Reset min max The...

Page 79: ...he edit field next to the telephone icon 2 Click in the box to the left the contact person or group you would like to be notified in the event of an alert in the given zone After You Finish Make sure...

Page 80: ...configuring click on the record icon NOTE The time remaining to record the audio label starts counting down once you press the record button Tip For consistency use the same words as you used when gi...

Page 81: ...n certain installations you have to adjust the low or high ohm trouble calibration to avoid constant false trouble alerts In edit mode under the Calibration tab enter the desired value in the edit fie...

Page 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...

Page 83: ...Viewing Zone Calibration Naming the Zone with a Text Label The zone text label is a name you give to a zone to facilitate its identification In addition to the zone number the text label appears ever...

Page 84: ...the type of end of line resistors used in your installation for the zone you are configuring to ensure data accuracy 1 In edit mode under the General tab click on the edit field next to EOLR 2 Select...

Page 85: ...b click on the at home arming button The green LED lights when the at home arming is enabled Activating the Chime on an Intrusion Zone Type In edit mode under the General tab click on the box next to...

Page 86: ...mail addresses but first be entered in the Menu System Contacts to be available for selection 1 In edit mode under the Action tab of the zone you are configuring click on the edit field next to the e...

Page 87: ...ral tab 2 State the zone audio label clearly NOTE The recording stops when it has reached the allowed time of 8 seconds 3 Click on the play icon to listen to the recording 4 If the recording is not sa...

Page 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...

Page 89: ...r when servicing Use the included nut and bolt or a padlock not included to lock the enclosure Once a year open and inspect the enclosures for moisture or dust build up Using a damp cloth wipe clean t...

Page 90: ...placement is completed 5 Close the circuit of the main sector voltage Replacing the Battery At some point the battery will need to be changed Properly doing so ensures the system functions properly Be...

Page 91: ...uto test to end the testing Testing Communication With the Contacts Testing communication methods with the contacts ensures the messages reach the contacts in the event of an alert Before You Begin NO...

Page 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...

Page 93: ...ltage at the AA128 Touch supply input terminals 24Vdc minimum at J13 between VDC and VDC If the problem persists contact your dealer The siren output is disconnected Make sure the load connected to th...

Page 94: ...art On first startup the controller needs to be powered by the main sector The system does not detect any probe Make sure the flat cable between the top and the bottom board inside the enclosure is pr...

Page 95: ...ends after a user defined delay On Site Listening delay it cannot end sooner The system cannot recognize my password or selection over the phone Phone compatibility If the AA128 Touch does not recog...

Page 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...

Page 97: ...3 4 ZONE4 ZONE5 AGND5 6 ZONE6 ZONE7 AGND7 8 ZONE8 EXT MIC Inputs for an external microphone EXT MIC EXT MIC SHIELD SBI Serial bus interface communication bus Wired between the main system and optional...

Page 98: ...er cable from power pack TEMP_BATT BATT Battery power supply inputs through power cable from power pack BATT VDC Line power supply inputs through power cable from power pack VDC TIP LINE Phone connect...

Page 99: ...0 AWG 600 V 75 C 167 F UL AWM or CM ttype 20 AWG 600 V 75 C 167 F Maximum length 36 inches Wire specifications for battery connections to the power supply Item Description Certification and type CSA T...

Page 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...

Page 101: ...les All other low voltage devices Table C 1 Low voltage cable specifications Item Description Cable type Twisted and shielded Minimum gauge 1 mm2 18 AWG Maximum sensor cable length including any cable...

Page 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...

Page 103: ...ed lead acid 12V 7 0AH OUTPUTS RELAY 1 2 28Vdc 4A max SERIAL BUS 28Vdc 2A max SIREN 12Vdc 1 5A max 12VDC 12Vdc 750mA max 28VDC 28Vdc 350mA max Main supply voltage fluctuations shall not exceed 10 of t...

Page 104: ...T2 Faston Tab 250 Storage temperature 20 C to 40 C 4 F to 104 C Battery the values shown are based on ambi ent temperatures of 20 25 C 68 77 F Type Sealed lead acid battery Power output 12 VDC 7 5 Ah...

Page 105: ...nics part description Refer ence Fuse recommended by the manufacturer Recommended fuse model 127 00031 Fuse 2 5A slowblow 5X20MM 250V F27 F28 Bel Fuse 5HT 2 5 R 127 00032 Fuse 1A slowblow 5X20MM 250V...

Page 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...

Page 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...

Page 108: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a DPST disconnect switch 108 895 00677 Agri Alert 128 Touch...

Page 109: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a SPST disconnect switch 895 00677 Agri Alert 128 Touch 109...

Page 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...

Page 111: ...0 FCC part 15 under part B 2012 Group 1 class A Class A 2 Radiated emissions CISPR 11 2009 A1 2010 FCC part 15 under part B 2012 Group 1 class A Class A 3 Harmonic current emissions IEC61000 3 2 2006...

Page 112: ...50 1 second edition and CAN CSA C22 2 no 60950 1 second edition in the section 6 NSI TIA 968 B Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipme...

Page 113: ...r wait time 42 chime 85 cleaning the controller 89 communication testing 91 configuration 78 84 calibration zero calibration span setting the calibration zero 63 73 zone 45 4 20 mA minimum and maximum...

Page 114: ...how it works outdoor temperature compensation 52 I industry canada 9 initializationmodules managing 40 modules 40 input sensor selection 48 58 68 76 84 inspecting the controller 89 installation requir...

Page 115: ...39 selecting units of measure 60 70 sensor connecting 28 sensor cabling installation requirements 101 silence detection 42 siren connecting 26 enabling 54 61 71 79 86 software updating management 37...

Page 116: ...Index Z zone audio name 55 62 72 80 87 zone name 47 57 67 75 83 zone settings 45 zone type selection 45 48 58 68 76 84 zones filtering 32 116 895 00677 Agri Alert 128 Touch...

Page 117: ...ogos and Definition Electrical safety approval in North America of the sealed lead acid battery Electrical safety approval of the product in North America Canada and USA European conformity Recycling...

Page 118: ......

Page 119: ...month from the date of purchase extended warranty period During the extended warranty period GSI will replace the frame or basket components that prove to be defective under normal conditions of use w...

Page 120: ...refully followed in all cases Authorities having jurisdiction should be consulted before installations are made 1004 E Illinois St Assumption IL 62510 0020 Phone 1 217 226 4421 Fax 1 217 226 4420 www...

Reviews: