2
Getting Started
Topics Covered in this Chapter
Special Tools Needed for Installation
Guidelines on the Ideal Location for Installation
Correctly Supporting and Routing Cables
Special Tools Needed for Installation
The following tools are needed for the installation of your system:
• Hammer and punch to remove the knockouts at the bottom of the enclosures.
• Silicone caulking to seal the module mounting screws.
Guidelines on the Ideal Location for Installation
Consider the environment, mounting recommendations, and clearance space to choose the ideal location
for your system.
Operating Environment
• To avoid exposing the system to harmful gases or excessive humidity, install the system modules in a
corridor or a room dedicated to electronic controllers.
• The ideal ambient temperature is between 20 °C and 25 °C (68 °F - 77 °F). The temperature should
not go lower than 0 °C (32 °F) and should not exceed 40 °C (104 °F).
• Ensure there is sufficient ventilation around the unit.
• Install the modules far from sources of vibrations and where it is not likely to get bumped.
IMPORTANT:
If you are not planning on installing the system immediately, store the modules in a cool dry
place.
Requirements for the Mounting Structure
Mount the system into the supporting structure behind a drywall. If this is not possible, install pieces of
wood that can be screwed into the back structure and install the units on the pieces of wood.
Clearance Around the System Modules
The following minimum clearances must be respected around both the main system and the battery
enclosure.
• 305 mm (12 inches) above the modules to allow opening of the cover.
• 305 mm (12 inches) below the modules to leave room for the wiring.
• 305 mm (12 inches) between the modules to avoid electromagnetic interference.
895-00677
Agri Alert 128 Touch
15
Summary of Contents for 890-00584
Page 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Page 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Page 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Page 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Page 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Page 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Page 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Page 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Page 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Page 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Page 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Page 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Page 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Page 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Page 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Page 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Page 118: ......