Grundfos SSL 1.4 C Installation And Operating Instructions Manual Download Page 6

6

10. Negative-head pumps 

Pump types: 

STN, SSN and STL 2.0 CN.

10.1 General

Automatic negative-head shower pumps are designed to operate 
automatically in installations where the pumped system outlets 
are above the stored water level.
Shower pumps, types STN and SSN, feature independent 
pressure and flow controls, with built-in non-return valves and 
stainless-steel expansion tanks in each pump end. This system 
ensures complete hot- and cold-water system isolation with 
stable control over a very wide flow range.
The pump is fitted with dry-running protection. Should the water 
supply fail, the pump will stop to prevent damage to the shaft 
seals.

10.2 Dry-running protection

STN, SSN and STL 2.0 CN negative-head pumps feature dry-
running protection to avoid damage to seals caused by water 
starvation. This condition is possible if there is insufficient stored 
water or the pump strainers are blocked.
If the pump runs for 60 seconds with an insufficient water supply, 
the pump will stop and "lock out".

Resetting the "lock out"

To reset the pump, switch the electricity supply off for 
10 seconds. 
When the electricity supply is switched on again, the pump will 
run for a few seconds to recharge the tanks. If it continues to run 
and there is no demand, this would indicate that one of the 
following is still present:
• No water in the system.
• Blocked strainer.
• Air which has not yet cleared.

10.3 Connecting the pump

For the pump to work correctly, it must have:
• Air-free supply of hot water – the use of Surrey flanges is 

recommended.

• 22 mm (minimum) feed pipes, gate valves and flexible hoses.
• Minimum head of water to supply the pump 2 metres (6'6"). 

However, the STN and SSN pumps will function with a supply 
head as low as 600 mm (2 ft), providing the water make-up 
system has unrestrictive pipework, and provision is made to 
avoid air locks.

• Maximum hot-water temperature of 60 °C conforming to 

BS 6700: 2006.

• Maximum static head of 8 m, i.e. the highest point of the 

system must be less than 8 m above the pump. See fig. 4, 
page 14.

10.4 Installation instructions

• The hot-water cylinder must have an expansion pipe or be 

fitted with a vent pipe connected to the pump hot-water supply, 
to allow air from the hot-water cylinder to escape.
Excessive air entering the pump will cause faulty operation 
and damage to the pump seals which will cause serious water 
leaks.

• Feed pipes, hot and cold, must be minimum 22 mm with 

22 mm service isolating gate valves. The flexible hoses 
supplied 

must

 be used. The hoses must be connected without 

kinks which will restrict water flow. The maximum bend angle 
is 45 °.

• Ensure an adequate head of water and non-restrictive make-

up pipework. 
Inadequate feed head will cause pump cavitation, unstable 
water temperature, noise and ultimately pump and seal 
damage.

• All air must be thoroughly purged from the system. If air is 

present in the pump, it will be unable to generate sufficient 
pressure to operate the pressure switch. This will cause the 
pump to run or pulse continuously.

Lavatory cisterns

If the pump is to supply a lavatory cistern, certain precautions 
should be taken to avoid frequent starting and stopping of the 
pump due to low flow rates.
If possible, best practice is to supply the cistern from the 
mains water supply. Failing this, a "Torbeck" or equilibrium 
valve is recommended. If either of these are not possible, the 
following instructions should be followed:

– 

A: 

The pump is supplied with two expansion or pressure 

tanks. They have capacities of 500 ml and 160 ml. 

The larger tank must be used on the cold side of the 
pump

.

– 

B:

 The cistern filling pipework must be as free-flowing as 

possible with all flow restrictors removed.
It is possible to change the tanks from one side of the pump 
to the other. When doing so, take care to ensure that none 
of the fibre washers are lost.

Washer dryers

Only brass pumps must be used for these applications.

10.5 Pressure and flow control

Shower pumps for negative-head applications are controlled by 
both water pressure and water flow.
Twin-impeller pumps incorporate two separate pressure and flow 
control systems, one on each pump end, ensuring complete 
isolation of hot- and cold-water systems and consistent operation 
over a wide range of unbalanced flow rates.
The control system manifold includes an integral non-return valve 
to maintain system pressure when water is not flowing.

Operation

The pressure switches start the pump on falling pressure. 
The switch point is factory-set.

Once the pump has been started by the pressure switches, the 
flow switches maintain the pump running, providing the flow rate 
is above 0.4 l/min. When the flow rate drops below 0.4 l/min. or 
the demand is turned off, the pump will stop after first running on 
for 3 seconds to recharge the pressure tanks.

10.6 Operating instructions

Taps and valves used on the "pressure system" must be fully 
turned off when not in use.

10.7 Maintenance

Washers and seals must be replaced when necessary to prevent 
leaks or drips.
Any leak or drip will cause the pump to operate periodically, the 
frequency dependent on the rate of the leak.

Tank air-pressure setting

The pressures are factory-set. In the event of a leak, they should 
be set as follows:
The smaller tank (160 ml) should be set at a pressure between 
0.9 and 1.0 bar. The larger tank (500 ml) should be set at a 
pressure between 0.5 and 0.6 bar.

For further information regarding general maintenance and 
service, see section 

13. Service

.

Caution

Continued dry running will lead to overheating of 
the shaft seals and eventually to a water leak.

Caution

Do not connect the pump directly to the water 
mains supply. 

Note

It is important that the total head on the pump 
is less than 8 metres. Otherwise the pressure 
switch can never operate and hence the pump 
will fail to start.

Note

In certain applications, e.g. steam cabinets, it 
may be necessary to increase the pressure. 
Consult the appliance manufacturer.

Grundfos.bk  Page 6  Wednesday, September 3, 2008  1:36 PM

Summary of Contents for SSL 1.4 C

Page 1: ...Shower pump GRUNDFOS INSTRUCTIONS Installation and operating instructions Grundfos bk Page 1 Wednesday September 3 2008 1 36 PM...

Page 2: ...cil Directives on the approximation of the laws of the EC Member States relating to Machinery 98 37 EC Electrical equipment designed for use within certain voltage limits 2006 95 EC Standards used EN...

Page 3: ...4 Push fit connections SSN SSP STN and STP pumps The pump suction and discharge ports are fitted with push fit connections The flexible hoses supplied with the pump must be used Make sure that each ho...

Page 4: ...cold water supply to the hot water cylinder to prevent the supply of hot water only 7 Connecting the pump For ease of installation subsequent servicing and cleaning of strainers full bore isolating ga...

Page 5: ...ipes should have supplementary earth bonding Where the earth continuity has been broken the pump suction and discharge pipework should be connected with earthing clamps to BS 951 and 4 mm earthing wir...

Page 6: ...enerate sufficient pressure to operate the pressure switch This will cause the pump to run or pulse continuously Lavatory cisterns If the pump is to supply a lavatory cistern certain precautions shoul...

Page 7: ...in Increase the water flow to at least 0 5 l min 2 The flow from the shower drops a Blocked strainers Clean the pump strainers 3 The pump runs continuously a A tap or outlet is turned on Ensure there...

Page 8: ...strainers Clean the pump strainers 3 The pump runs continuously a A flow demand still exists Check the installation for leaks b Flow switch or reed switch faulty or incorrectly set Adjust or replace a...

Page 9: ...re 6 bar Minimum starting flow rate 0 5 l min Length 178 mm 178 mm 230 mm 245 mm 243 mm 266 mm 296 mm Width 135 mm 135 mm 135 mm 135 mm 135 mm 135 mm 135 mm Height 225 mm 225 mm 225 mm 225 mm 225 mm 2...

Page 10: ...3 bar Minimum starting flow rate 0 5 l min Length mm 275 mm 275 mm 225 mm 285 mm 285 mm Width mm 120 mm 120 mm 120 mm 120 mm 215 mm Height mm 185 mm 185 mm 185 mm 185 mm 256 mm Weight kg 4 6 kg 5 8 kg...

Page 11: ...this applies particularly to hard water areas 14 Disposal This product or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If thi...

Page 12: ...e Hot water cylinder Shower outlet 250 mm 10 inches below water level Shower valve Cold water storage tank of at least 50 gallon capacity Cold water supply min 22 mm System vent Surrey flange 22 mm se...

Page 13: ...water supply min 22 mm 230 V switched spur 22 mm service gate valves Pump Hot water supply Hot Cold Shower valve Supply to another shower if required Anti scald valve optional min 22 mm Min 2 metres...

Page 14: ...lange System vent Hot Cold Shower valve Supply to another shower bath or basin if required 230 V switched spur Cold water supply min 22 mm Pump Hot water supply min 22 mm 22 mm service gate valves Cis...

Page 15: ...391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps L...

Page 16: ...ww grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96787913 0908 GB Repl 96787913 1207 Grundfos bk Page 16 Wednesday September 3 2008 1 36 P...

Reviews: