Priority
Start/stop
button
Grundfos GO Remote or operating panel on
motor
Digital input
Bus communication
8
Maximum speed
/
User-defined
speed
9
Minimum speed
10
Start
11
Maximum speed
12
Minimum speed
13
Minimum speed
14
Start
15
Start
*
Stop
and
Maximum speed
settings made with Grundfos GO Remote or on the motor operating panel can be overruled by another operating-mode command
sent from a bus, for example
Start
. If the bus communication is interrupted, the motor resumes its previous operating mode, for example
Stop
, that was
selected with Grundfos GO Remote or the motor operating panel.
Related information
6.50 Factory settings for Grundfos GO Remote
Settings
MGE
MGE OEM
Setpoint
67 %
100 %
Operating mode
Normal
Normal
Set user-defined speed
67 %
67 %
Control mode
Constant curve
Constant curve
Buttons on product
Active
Active
Controller
Kp
: 0.5
Ti
: 0.5
Kp
: 0.5
Ti
: 0.5
Operating range
25-100 %
16-100 %
Ramps
Ramp-up time
: 1 s
Ramp-down time
: 3 s
Ramp-up time
: 10 s
Ramp-down time
: 10 s
Number
1
1
Radio communication
Activated
Activated
Analog input 1
Not active
Function
:
Setpoint influence
Measured parameter
:
Other
Signal type
:
0-10 V
Range
: 0-100
Unit
: %
Analog input 2
Not active
Not active
Analog input 3
Not active
Not active
Pt100/1000 input 1
Not active
Not active
Pt100/1000 input 2
Not active
Not active
Digital input 1
Ext. stop
Ext. stop
Digital input 2
Not active
Not active
Digital input/output 3
Not active
Reverse rotation
Digital input/output 4
Not active
Not active
Predefined setpoint
Not active
Not active
Analog output
Speed
/
0-10 V
Speed
/
0-10 V
External setpoint funct.
Not active
Linear
Signal relay 1
Alarm
Alarm
Signal relay 2
Ready
Ready
61
English (GB)