6.
Press the
Right
button to continue.
7.
Select
Wired GENIbus
as the communication method to be used between the two motors.
8.
Press the
Right
button twice to continue.
9.
Select the desired multimotor function. See
Multipump or multimotor function
.
10. Press the
Right
button to continue.
11. Press
OK
to search for other motors.
12. Select the additional motor from the list.
13. Press the
Right
button to continue.
14. Set
Time for pump changeover
.
This is the time at which the alternation between the two motors is to take place.
This step applies only if you have selected
Alternating operation, time
and if the motors are fitted with FM 300.
15. Press the
Right
button to continue.
16. Press
OK
to confirm the setting.
The multipump or multimotor function icons appear at the bottom of the operating panels.
6.46.5 Disabling a multipump or multimotor system with Grundfos GO Remote
1.
Go to
Assist
.
2.
Select
Multi-pump setup
and press
Disable
.
3.
Press the
Right
button to continue.
4.
Confirm the setting by pressing
Send
.
5.
Press
Finish
.
6.46.6 Disabling a multipump or multimotor system with the advanced operating panel
1.
Go to
Assist
.
2.
Select
Setup of multi-pump system
.
3.
Press the
Right
button to continue.
4.
Press
OK
to confirm
No multi-pump function
.
5.
Press the
Right
button to continue.
6.
Press
OK
to confirm.
6.47 "Description of control mode"
The function is only available in the advanced operating panel.
The function describes each of the control modes available for the product.
Related information
6.48 "Assisted fault advice"
This function provides guidance and corrective actions in the event of product failure.
6.49 Priority of settings
With Grundfos GO Remote, you can set the motor to operate at maximum speed or to stop.
If two or more functions are enabled at the same time, the motor operates according to the function with the highest priority.
If you have set the motor to maximum speed via the digital input, the motor operating panel or Grundfos GO Remote can only set the motor
to
Manual
or
Stop
.
The priority of the settings appears from the table below:
Priority
Start/stop
button
Grundfos GO Remote or operating panel on
motor
Digital input
Bus communication
1
Stop
2
Stop
3
Manual
4
Maximum speed
/
User-defined speed
5
Stop
6
User-defined speed
7
Stop
60
English (GB)
Summary of Contents for RADIOMODULE 2G4