PHP A-1 Instruction Manual /
Operation and display
25
USER LEVEL 3 ACTIONS:
Cart. change MWE
Cart. change MVE
After changing the softening
cartridge resp. the desalination
cartridge the change must
be confirmed.
Thus the remaining capacity will
be set anew due to the set water
hardness resp. water conductivity.
Start/stop
fast degassing
USER LEVEL 3 SETTINGS PRESSURE MAINTENANCE:
Working pressure
To set the desired working pressure
see Chapter 6 “commissioning”
- “Step 11”.
At double-pump systems (systems
Duo and Maxi) you can choose the
following operating modes:
• “pump M1 only”
Pump M2 is deactivated
permanently (e.g. for
maintenance works).
• “pump M2 only”
Pump M1 is deactivated
permanently (e.g. for
maintenance works).
•
“redundancy mode“
The actual priority pump starts
pressure-dependent. The
additional pump starts only in case
of an error of the priority pump.
•
“staggered mode“
(default setting
at systems Duo and maxi).
The actual priority pump starts
pressure-dependent. The
additional pump starts in case of
an error of the priority pump, also
it starts pressure-dependent.
• “parallel mode“
Priority pump and additional pump
always run at the same time.
Selection of the used level
measurement at devices with enabled
second level measurement L2:
• “automatic change”
Automatic change to the second
level measurement L2 in case of
identified electric faults at level
measurement L1 (at least one of
the error messages E12, E13,
E14, E15 must be released).
Operating. mode
pumps
Operating mode
level
• “level L1 only”
Only L1 is used for level
measurement
• “level L2 only”
Only L2 is used for level
measurement
USER LEVEL 3 SETTINGS MAKEUP:
Operating mode
Selection of the operating mode of the
enabled EMCF-1 V makeup module
• “amount-controlled”
If the set available amount is used
(see max. amount), error message
E26 will be released and the
makeup will be disabled.
• “time-controlled”
The set max. amount is available
within the set period “period for
amount”. If more than this amount
is used within this period, the error
message E26 will be released and
the makeup will be disabled.
Otherwise the entire amount “max.
amount” will be enabled for the
next period.
Set the max. amount in litres.
Set the period of time for operating
mode “time-controlled”.
Make-up starts below this level
(hysteresis: +10%)
measured hardness of the
makeup water
measured conductivity of the
makeup water
Max. amount
Period for amount
Level: start makeup
Water hardness
Water conductivity
Summary of Contents for PHP A-1 4.0
Page 1: ...PHP A 1 4 0 5 6 6 6 8 1 Instruction manual UK version original instructions...
Page 12: ...PHP A 1 Instruction Manual Wiring diagrams 4 Wiring diagrams 12 4 1...
Page 13: ...PHP A 1 Instruction Manual Wiring diagrams 13...
Page 14: ...PHP A 1 Instruction Manual Wiring diagrams 14...
Page 51: ...PHP A 1 Instruction Manual Appendix 51...
Page 52: ...PHP A 1 Instruction Manual EC declaration of Conformity 52 13 EC declaration of Conformity...