43
7. Applicable standards and directives
8. Operator’s accessory list
Prior to installation, the operator must purchase the following
accessories according to the product numbers in the Grundfos
Alldos data booklet and the technical data.
The data booklet is available on www.Grundfosalldos.com.
DIN EN
Applicable standards and directives
EN 809: 1998
Pumps and pump units for liquids -
Common safety requirements;
German version EN 809: 1998
EN 61000-3-2: 2006
Emitted interference
EN 61000-3-3
Emitted interference
EN 61326-1: 2006
Immunity to interference for the
industrial sector
EN 61326-1: 2006
Emitted interference Class B
DIN EN ISO 12100-1
and -2 (2004 - 04)
Safety of machinery -
Basic concepts, general principles for
design - Part 1: Basic terminology,
methodology (ISO 12100-1: 2003);
German version EN ISO 12100-1: 2003;
Part 2: Technical principles
(ISO 12100-2: 2003);
German version ISO 12100-2: 2003
(Replaces EN 292-1, -2)
DIN EN 938
Chemicals used for treatment of water
intended for human consumption -
Sodium chlorite
DIN EN 939
Chemicals used for treatment of water
intended for human consumption -
Hydrochloric acid
DIN EN 12671: 2007
Chemicals used for treatment of water
intended for human consumption
• Chlorine dioxide generated in situ;
German version EN 12671: 2007,
• Chlorine dioxide;
German version EN 12671: 2000
98/37/EC
Machinery directive
2006/95/EC
Low voltage directive
DVGW worksheet
W224
W624
Dosing of a chlorine dioxide solution
generated in situ for the purpose of
disinfection
GUV-V D05
Regulation for the prevention of
accidents
"Chlorination of Water" of the
Rheinischer
Gemeindeunfallversicherungsverband
Heyestraße 99
40625 Düsseldorf, Germany
dated April 1979 in the version dated
January 1997, valid since 1st January
1997
TrinkwV 2001
Drinking water ordinance, valid since
January 2003
Accessories to be purchased
Available
from
Grundfos
Alldos
1. Container with diluted HCl (diluted
concentration of 9.0 % by weight in
accordance with DIN EN 939)
No
2. Container with diluted NaClO
2
(diluted
concentration of 7.5 % by weight in
accordance with DIN EN 938)
No
3. Two collecting trays for chemical containers
Yes
4. Inductive or ultrasound flow meter,
if necessary
Yes
5. Connection cable, if necessary
Yes
For dilution water line (if no mixing module with
dilution water connection has been ordered):
6. Tapping sleeve
Yes
7. Double nipple
No
8. Ball valve
No
9. Hose connection for dilution water hose
No
For main water line:
10. Tapping sleeve for injection unit
Yes
11. Two tapping sleeves for extension module,
if necessary
Yes
12. Tapping sleeve for sample-water bleeding
Yes
13. Sample-water filter (in case of insufficient
water quality)
Yes
Oxiperm Pro hoses:
14. Hose between dilution water and solenoid
valve
Yes
15. Dosing line between dosing pump and
injection unit
Yes
Measuring cell hoses:
16. Hose between measuring cell and sample-
water bleeding point
Yes
17. Hose between measuring cell and drain
Yes
For mixing module, if installed:
18. Hose between mixing module and main water
line and hose back to mixing module
Yes
19. Dosing line between dosing pump and
injection unit in mixing module
Yes
Or for measuring module, if installed:
Yes
20. Hose between measuring module and main
water line and hose back to measuring
module
Yes
21. Protective tube for dosing hose
No
22. Main switch
No
Cables:
23. Oxiperm Pro power supply cable
No
24. Cable for measuring module or mixing
module, if necessary
No
25. Protective clothing (in accordance with
German GUV-V D05)
Yes
26. Two 10-litre plastic buckets
No
27. 100 g sodium thiosulphate (20 g per flushing
process)
No
Summary of Contents for Oxiperm Pro OCD-162-10