background image

31

17. Start-up

Prior to start-up, the connection and DIP switch setting must have 
been carried out according to sections 

13.

 to 

16.

Start-up must be carried out by authorized personnel.

Proceed as follows:

1. Check whether the electrodes have been connected according 

to the wiring diagram for the actual application.

2. Check that the pump inlets are submerged in the liquid to be 

pumped.

3. Set the motor protection relays to the rated current stated on 

the nameplates.

4. Warning:

5. Switch on the electricity supply.

Three-phase pumps only:

 Check for wrong phase sequence 

(the pump cannot be started if the phase sequence is wrong!).

6. Start the pumps, see section 

13.5

14.5

15.5

 or 

16.5

.

7. Check that the pumps are not running dry. The risk of dry run-

ning can be eliminated by a renewed time setting by means of 
the DIP switch (stop delay) according to section 

13.2

14.2

15.2

 or 

16.2 and/or 

by moving/shortening the electrodes.

8.

Three-phase pumps only:

 Check whether the direction of 

rotation of the pumps is correct according to the installation 
and operating instructions for the pumps in question.

9. Select the required operating mode by means of the ON-OFF-

AUTO selector switch, see section 

13.5

14.5

15.5

 or 

16.5

.

18. Maintenance

During normal application and operation, the LCD 110 controller 
is maintenance-free.

However, it is advisable to carry out minor checks of the LCD 110 
controller, pump pits, tanks, pumps, etc. at suitable intervals. 
These checks should be carried out by authorized personnel. 

Check the gaskets of the LCD 110 cabinet front and those of 
the Pg cable entries.

Check for possible deposits/sludge build-up in the pump pit/
tank. Sludge may settle in areas with almost stagnant liquid.

Check for beginning sludge build-up around the electrodes. 

Check for possible blockage on the suction side of the pump. 
A blockage will typically be a large solid object.

If the LCD 110 has been installed in a particularly aggressive 
environment, it is advisable to check the motor protection con-
tacts in order to identify possible chemical attack resulting in 
corrosion. In typical installations, the motor protection contacts 
will work for several years and do not require any inspection.

Note:

 The list above is 

not

 complete. The LCD 110 may be 

installed in systems, installations and/or environments which 
require thorough and regular maintenance.

19. Technical data – LCD 110

Voltage variants, nominal voltages

1 x 230 V.

3 x 400 V.

Voltage tolerances

–15%/+10% of nominal voltage.
See also installation and operating instructions for the pump in 
question.

Mains frequency 

50/60 Hz.
See also installation and operating instructions for the pump in 
question.

Supply system earthing

For TN systems and TT systems.

Rated insulation voltage, U

i

4 kV.

Rated impulse withstand voltage, U

imp

4 kV.

Back-up fuse

Depending on variant, see nameplate.

Control circuit fuse

Fine-wire fuse: 250 mA / F / 32 mm x ø6 mm.

Ambient temperature

During operation: –30 to +50 °C
(must not be exposed to direct sunlight).

In stock: –30 to +60 °C.

Enclosure class

IP 65. 

EMC (electromagnetic compatibility)

According to EN 61 000-6-2 and EN 61 000-6-3.

LCD 110 cabinet 

External dimensions: 
Height = 410 mm, width = 278 mm, depth = 150 mm.

Material: Technopolymer and polycarbonate.

Weight: Approx. 5 kg, depending on variant, see nameplate.

Outputs for alarm devices

Max. 230 VAC / max. 2 A / min. 10 mA / AC1.

Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous 
to health, thorough cleaning/venting of pumps, pits, 
etc. must be carried out according to local regula-
tions.

Before making any connections in the LCD 110 or 
work on pumps, pits, etc., it must be ensured that the 
electricity supply has been switched off and that it 
cannot be accidentally switched on. 

Set the motor-protective circuit breakers to the rated 
current stamped on the nameplates. 

Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous 
to health, thorough cleaning/venting of pumps, pits, 
etc. must be carried out according to local regula-
tions.

Before making any connections in the LCD 110 or 
work on pumps, pits, etc., it must be ensured that the 
electricity supply has been switched off and that it 
cannot be accidentally switched on. 

Summary of Contents for LC 110

Page 1: ...LC 110 LCD 110 GRUNDFOS INSTRUCTIONS Installation and operating instructions LC 110 LCD 110...

Page 2: ...bereinstimmen Maschinenrichtlinie 2006 42 EG Norm die verwendet wurde EN 60204 1 2006 Niederspannungsrichtlinie 2006 95 EG Norm die verwendet wurde EN 60439 1 2004 EMV Richtlinie 2004 108 EG Normen di...

Page 3: ...3 LC 110 LCD 110 Installation and operating instructions 4 Montage und Betriebsanleitung 33 Monterings og driftsinstruktion 68...

Page 4: ...a LCD 110 31 20 Fault finding chart 32 21 Disposal 32 1 General LC 110 The LC 110 controller is designed for the control of pumps in wastewater water supply and drainage systems Type key 1 1 Applicati...

Page 5: ...lems with the signal values sent back to the controller may arise In such cases it is recommended to use float switches Note Cables of up to 100 metres can be connected between the controller and the...

Page 6: ...arm resetting switch 9 selection of automatic restarting switch 10 Fig 3 Set the DIP switch as shown in fig 3 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The...

Page 7: ...pump Restarting will not be carried out until the motor has cooled to normal temperature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this sett...

Page 8: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Page 9: ...estarting switch 10 Fig 5 Set the DIP switch as shown in fig 5 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to other switch com...

Page 10: ...ed out until the motor has cooled to normal tem perature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted m...

Page 11: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Page 12: ...automatic restarting switch 10 Fig 7 Set the DIP switch as shown in fig 7 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to othe...

Page 13: ...ted is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the pump To restart the pu...

Page 14: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO...

Page 15: ...ossible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The above list is not complete...

Page 16: ...N OFF AUTO selector switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 1 d The motor protection relay h...

Page 17: ...s Section 14 Systems for parallel operation with 4 levels 5 electrodes Section 15 Systems for 100 standby operation with 4 levels 5 electrodes Section 16 Systems for full control operation with 4 leve...

Page 18: ...instructions of the pump Key to the symbols in fig D1 on page 100 TM02 2349 4101 Pos Description 1 Module CU 214 2 Terminal block for level inputs 11 12 22 32 and 42 3 Terminal block with input for th...

Page 19: ...itched off for at least 1 minute TM016870 2308 This setting determines the actual application type par allel operation with 3 levels 4 electrodes page 100 At this setting the start up is delayed withi...

Page 20: ...hing TM02 4643 1402 Pos Description 1 Green indicator light for pump 1 and 2 indicating start ing delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and 2 indicating pum...

Page 21: ...switch registers overtemperature OFF middle position The pump cannot start when the selector switch has been set to this position The alarm memory is reset by pushing the selector switch into position...

Page 22: ...etting switch 9 selection of automatic restarting switch 10 Fig 13 Set the DIP switch as shown in fig 13 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP...

Page 23: ...When the pumps connected are used in explosion hazard areas switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the p...

Page 24: ...f 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means...

Page 25: ...re the correct configuration during start up after change of the DIP switch setting The DIP switch setting offers the following possibilities selection of starting delay and automatic test run switch...

Page 26: ...must be reset manually by means of the reset button the reset button is described in section 15 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarti...

Page 27: ...electricity supply switched on is off 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the al...

Page 28: ...larm resetting switch 9 selection of automatic restarting switch 10 Fig 17 Set the DIP switch as shown in fig 17 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note...

Page 29: ...scribed in section 16 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarting will not be carried out until the motor has cooled to normal temperatur...

Page 30: ...r switch see position OFF Even if the fault condition still exists the external alarm devices and the built in buzzer will be reset when the reset button is pressed The ON OFF AUTO selector switch for...

Page 31: ...r to identify possible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The list above i...

Page 32: ...or switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 9 d The motor protection relays have cut out the...

Page 33: ...4614 2308 M Ext max 230V max 2A H NC H COM H NO G NC G COM G NO ref 2 LC 110 1 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1 T2 3 3 L1 L2L3...

Page 34: ...10 M Ext 1 2 ref 3 max 230V max 2A H NC H COM H NO G NC G COM G NO ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1...

Page 35: ...max 230V max 2A H NC H COM H NO G NC G COM G NO LC 110 1 2 ref 3 4 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T...

Page 36: ...C H COM H NO G NC G COM G NO T12 T22 32 LC 110 1 2 ref 3 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M 1U2 1V2 1W2...

Page 37: ...C H COM H NO G NC G COM G NO LCD 110 T11 11 12 22 32 42 T21 T12 T22 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Page 38: ...x 2A ON DIP 1 2 3 4 5 6 7 8 9 10 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Page 39: ...DIP 1 2 3 4 5 6 7 8 9 10 LCD 110 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Page 40: ...5 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS...

Page 41: ...d makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark A...

Reviews: