4.4.2 Reduction in connection with long motor cables
12.4 Electrical data
Mains supply (L1, L2, L3)
Supply voltage
200-240 V ± 10 %
Supply voltage
380-500 V ± 10 %
Supply voltage
525-600 V ± 10 %
Supply voltage
525-690 V ± 10 %
Supply frequency
50/60 Hz
Maximum temporary imbalance
between phases
3 % of rated value
Leakage current to protective
earth
> 3.5 mA
Number of cut-ins, enclosure A
Max. 2 times/min
Number of cut-ins, enclosures B
and C
Max. 1 time/min
Do not use the power supply for switching CUE on and
off.
Motor output (U, V, W)
Output voltage
0-100 %
Output frequency
0-590 Hz
Switching on output
Not recommended
1
Output voltage in percentage of supply voltage.
2
Depending on the pump family selected.
RS-485 GENIbus connection
Terminal number
68 (A), 69 (B), 61 GND (Y)
The RS-485 circuit is functionally separated from other central
circuits and galvanically separated from the supply voltage (PELV).
Digital inputs
Terminal number
18, 19, 32, 33
Voltage level
0-24 VDC
Voltage level, open contact
> 19 VDC
Voltage level, closed contact
< 14 VDC
Maximum voltage on input
28 VDC
Input resistance, R
i
Approx. 4 kΩ
All digital inputs are galvanically separated from the supply voltage
(PELV) and other high-voltage terminals.
Signal relays
Relay 01, terminal number
1 (C), 2 (NO), 3 (NC)
Relay 02, terminal number
4 (C), 5 (NO), 6 (NC)
Maximum terminal load (AC-1)
240 VAC, 2 A
Maximum terminal load
(AC-15)
240 VAC, 0.2 A
Maximum terminal load (DC-1)
50 VDC, 1 A
Minimum terminal load
24 VDC, 10 mA
24 VAC, 20 mA
1
IEC 60947, parts 4 and 5.
C
Common
NO
Normally open
NC
Normally closed
The relay contacts are galvanically separated from other circuits by
reinforced insulation (PELV).
Analog inputs
Analog input 1, terminal number 53
Voltage signal
Voltage range
Input resistance, R
i
Maximum voltage
A53 = "U"
0-10 V
Approx. 10 kΩ
± 20 V
Current signal
Current range
Input resistance, R
i
Maximum current
A53 = "I"
0-20, 4-20 mA
Approx. 200 Ω
30 mA
Maximum fault
0.5 % of full scale
1
The factory setting is voltage signal "U".
Analog input 2, terminal number 54
Current signal
A54 = "I"
Current range
0-20, 4-20 mA
Input resistance, R
i
Approx. 200 Ω
Maximum current
30 mA
Maximum fault
0.5 % of full scale
All analog inputs are galvanically separated from the supply voltage
(PELV) and other high-voltage terminals.
Analog output
Analog output 1, terminal
number
42
Current range
0-20 mA
Maximum load to frame
500 Ω
Maximum fault
0.8 % of full scale
The analog output is galvanically separated from the supply voltage
(PELV) and other high-voltage terminals.
MCB 114 sensor input module
Analog input 3, terminal number 2
Current range
0/4-20 mA
Input resistance
< 200 Ω
Analog inputs 4 and 5, terminal
number
4, 5 and 7, 8
Signal type, 2- or 3-wire
Pt100/Pt1000
Related information