![Grundfos CU 362 Installation And Operating Instructions Manual Download Page 17](http://html1.mh-extra.com/html/grundfos/cu-362/cu-362_installation-and-operating-instructions-manual_2271080017.webp)
7. The "Alarm" menu
This display shows an overview of the submenus of the "Alarm"
menu.
In this menu, it is possible to see existing alarms, to reset alarms
and to see the alarm log.
A system fault
or a monitored component can generate an alarm
or a warning
in addition to the fault indication via the alarm/
warning relay and the red indicator light on CU 362.
An alarm can cause a change of the operating mode, for
example from start to stop.
A warning is reported, but it does not cause the system to stop.
Path:
Alarm > Alarm status
3_ALARM_ST
A
TUS_003
Alarm status
Related information
7.1 Current alarms
This display shows all active system warnings and alarms.
An alarm can only be reset when it is no longer active. An alarm
can be reset when date and time are given to the right of
"Disappeared at". Press [OK] to reset all alarms that have
disappeared.
See section about alarm log.
Symbol
Description
Alarm
Warning
System fault
This menu shows the following:
•
Warnings caused by faults that still exist.
•
Warnings caused by faults that have disappeared, but the
warning requires manual resetting.
•
Alarms caused by faults that still exist.
•
Alarms caused by faults that have disappeared, but the alarm
requires manual resetting.
All warnings and alarms with automatic resetting are automatically
removed from the menu when the fault has been corrected.
Alarms requiring manual resetting are reset in this display by
pressing [OK].
For every warning or alarm, the following is shown:
•
Whether it is a warning or an alarm (see symbols in the table
above).
•
Where the fault occurred: System, Pump 1, Pump 2, etc.
•
What the cause of the fault is, and the alarm code in
brackets, for example: High level (191).
•
When the fault occurred: Date and time.
•
When the fault disappeared: Date and time. If the fault still
exists, date and time are shown as --...--.
The latest warning or alarm is shown at the top of the display.
Path:
Alarm > Alarm status > Current alarms
3-1_CURRENT_ALARMS_008
Current alarms
Related information
7.2 Alarm log
The alarm log can store up to 24 warnings and alarms.
For every warning or alarm, the following is shown:
•
Whether it is a warning
or an alarm
.
•
Where the fault occurred: System, Pump 1, Pump 2, etc.
•
In the case of an input-related fault, the input appears.
•
What the cause of the fault is, and the alarm code in
brackets, for example: Conflicting levels (204).
•
When the fault occurred: Date and time.
•
When the fault disappeared: Date and time. If the fault still
exists, date and time are shown as --...--.
The latest warning or alarm is shown at the top of the display.
Example
The display shows one warning and three alarms, two of which are
still active.
To reset alarms, see section about current alarms.
An alarm cannot be reset until the fault has been
corrected.
Path:
Alarm > Alarm status > Alarm log
3-2_ALARM_LOG_009
Alarm log
Related information
17
English (GB)