![Grundfos CU 3 2 Series Installation And Operating Instructions Manual Download Page 9](http://html1.mh-extra.com/html/grundfos/cu-3-2-series/cu-3-2-series_installation-and-operating-instructions-manual_2271076009.webp)
English (GB)
9
5. Mechanical installation
Fasten the CU 3X2 with the four screws, M5 x 10,
supplied with the unit (pos. 1).
Maximum torque: 1.4 Nm.
Dimensions of the CU 3X2, see section
.
Fig. 7
Mounting in panel front (standard)
Connect the earth terminal (between the cable
clamps) on the CU 3X2 to the mounting frame
(pos. 2, fig.
). See fig.
Fig. 8
Earth connection
6. EMC-correct installation
The CU 3X2 is normally mounted in a panel which
also contains an IO 351 module, contactors and
other power equipment. The panel can also contain
other Grundfos modules and frequency converters.
In order to ensure faultless operation, it is very
important to install the electronic modules in an
EMC-correct way:
•
Ensure a sufficient earth connection between the
CU 3X2 and the frame. See fig.
.
•
Use screened cables for GENIbus. Connect the
screen to the cable clamp of the CU 3X2 in front
of the terminals A1, Y1 and B1. See fig.
.
Also use screened cable for the CIM module.
Fig. 9
Screen fixed with cable clamp
•
Signal conductors for digital and analog inputs
and outputs should be screened, i.e. run the
screen all the way to the CU 3X2 and connect it
to frame with for instance a cable clamp.
Do not twist screen ends to avoid pig tails, as this
will destroy the screen effect at high frequencies.
Use cable clamps instead.
TM
03
130
1
410
5
Note
In order to achieve enclosure class IP55,
the CU 3X2 must be mounted in a panel or
cabinet.
TM
0
4
2
066
1
908
Min. 1.5 mm
Max. 3 mm
TM
04
20
65
19
08
Note
Any isolating plastic tape between screen
and sheath must be removed before
mounting the cable in the cable clamp.
Summary of Contents for CU 3 2 Series
Page 2: ...2...
Page 277: ...CN 277 6 CU 3X2 IO 351 CU 3X2 8 GENIbus A1 Y1 B1 CU 3X2 9 CIM 9 CU 3X2 TM04 2065 1908...
Page 299: ...KO 299 6 EMC CU 3X2 IO 351 EMC CU 3X2 8 GENIbus A1 Y1 B1 CU 3X2 9 CIM 9 CU 3X2 TM04 2065 1908...
Page 306: ...Arabic AR 306 1 4 14 TM04 2068 1908 1 8 18 1 5 15 1 1 2 2...
Page 318: ...Appendix 318 Appendix 1 RoHS W W W y K K K K K y K K K K K d K d y d...