Grundfos CIU 251 Instructions Manual Download Page 3

English (GB)

3

2. Modbus register mapping

2.1 CIU 251 register blocks

2.2 IO 270 registers

Register

Description

Module/device

00001

CIM configuration

Related to the CIM module

00021

CIM status

00030

GENIpro device family/type/version

00101

Device control

Device data area of the connected Grundfos product

00201

Device status

00301

Device data

00701

Device alarm simulation

00801

Name register area

Not supported by all products

01001

GENIpro request telegram

Reserved for GENIpro communication via Modbus

01101

GENIpro reply telegram

01201

IO 270 control

Related to the IO 270 module related 
(covered by this manual)

01211

IO 270 status

01221

IO 270 data

Address

Modbus name

Scale

Modbus description

Control

1201

IO270_SetAnalogOutput

0.1 %

Control of analog output value
(Value change triggered)

01202

IO270_SetRelayOutput

Bool

Control of output relay
(Value change triggered)
Bit

Description

0

0 = Open relay, 1 = Closed relay

01203

IO270_LevelShiftCountControl

Bits

Reset of digital input shift counters and level duration counters
(Rising edge triggered).
Bit

Description

0

0 = No action, 1 = Clear DI1 duration counters

1

0 = No action, 1 = Clear DI1 shift counter

2

0 = No action, 1 = Clear DI2 duration counters

3

0 = No action, 1 = Clear DI2 shift counter

4

0 = No action, 1 = Clear DI3 duration counters

5

0 = No action, 1 = Clear DI3 shift counter

6

0 = No action, 1 = Clear DI4 duration counters

7

0 = No action, 1 = Clear DI4 shift counter

Status

01211

IO270_AnalogIn1Fault

Bits

Sensor faults, analog input 1
Bit

Description

0

0 = No fault, 1 = Signal current too high (> 20 mA)

1

0 = No fault, 1 = Signal current too low (< 4 mA)

2

0 = No fault, 1 = Signal voltage too high

3

0 = No fault, 1 = Sensor power supply fault

01212

IO270_AnalogIn2Fault

Bits

Sensor faults, analog input 2
Bit

Description

0

0 = No fault, 1 = Signal current too high (> 20 mA)

1

0 = No fault, 1 = Signal current too low (< 4 mA)

2

0 = No fault, 1 = Signal voltage too high

3

0 = No fault, 1 = Sensor power supply fault

01213

IO270_TempInStatus

Bits

Sensor faults, temperature
Bit

Description

0

0 = No fault, 1 = No sensor

1

0 = No fault, 1 = Short-circuit

2

0 = No fault, 1 = PT1000 sensor connected

3

0 = No fault, 1 = PT100 sensor connected