5.7 Alarm simulation register block
Registers in this register block can be read by means of function codes 0x03 and/or 0x04.
5.8 User register block
Address
Register name
Description
00701
SimulationWarningBits1
Used to generate simulated alarms/warnings.
Simulated alarms and warnings can be cleared with the ResetAlarm control bit (register 00101,
bit 0) or by pressing the "R" button on the MP 204. Bit interpretation like WarningBits1
(register 00205) and WarningBits2 (register 00206).
00702
SimulationWarningBits2
00703
SimulationAlarmBits1
00704
SimulationAlarmBits2
Address
Register name
Scale
Description
00751-
00800
UserRegisters
unscaled
This area is for device labelling by the user (SCADA system).
The CIU 250 will not modify this area by itself.
The user register values are stored in the device and will remain after a power-
off.