English (GB)
7
5. Modbus RTU, CIM 200 setup
Fig. 4
CIM 200 Modbus module
A screened, twisted-pair cable must be used. The cable screen
must be connected to protective earth at both ends.
Recommended connection
5.1 Setting the Modbus transmission speed
The transmission speed must be set correctly before the CIM 200
Modbus module is ready to communicate with the Modbus
network. DIP switches SW4 and SW5 are used for setting the
transmission speed. See fig.
.
Fig. 5
Modbus transmission speed
DIP switch settings
Available transmission speeds in bits/s: 1200, 2400, 4800, 9600,
19200 and 38400.
The first three transmission speeds are only available via
software settings, whereas the last three are available via DIP
switches.
Default transmission speed is 19200 bits per second, as per the
Modbus RTU standard.
Software-defined
When SW4 and SW5 are set to "software-defined", writing a
value to the holding register at address 00004 will set a new
transmission speed.
Use the following values for software-defined transmission
speeds:
This value is set to 1200 bits/s as default.
The communication interface does not support transmission
speeds above 38400 bits/s.
The software-defined transmission speed value will be stored in
the communication interface and will remain after a power-off.
TM
04
16
97
09
08
Pos.
Designation
Description
1
D1
Modbus terminal D1 (positive
data signal)
2
D0
Modbus terminal D0 (negative
data signal)
3
Common/GND
Modbus terminal
Common/GND
4
SW1/SW2
On/off switches for termination
resistor
5
SW3/SW4/SW5
Switches for selection of Modbus
parity and transmission speed
6
LED1
Red/green status LED for
Modbus communication
7
LED2
Red/green status LED for
internal communication between
the CIM 200 and the Grundfos
product
8
SW6
Hex switch for setting the
Modbus address (four most
significant bits)
9
SW7
Hex switch for setting the
Modbus address (four least
significant bits)
Modbus terminal
Colour code
Data signal
D1-TXD1
Yellow
Positive
D0-TXD0
Brown
Negative
Common/GND
Grey
Common/GND
1
2
3
4
5
6
7
8
9
TM
04
17
10
09
08
Transmission speed [bits/s]
SW4
SW5
9600
OFF
ON
19200
OFF
OFF
38400
ON
OFF
Software-defined
ON
ON
Software-defined transmission
speed
Value to set in register
00004
1200 bits/s
0
2400 bits/s
1
4800 bits/s
2
9600 bits/s
3
19200 bits/s
4
38400 bits/s
5