9.9.3 Block names, DLC, float-switch-controlled option
The following block names are used.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your
application.
Example, changing adjustable parameter blocks, DLC, float-controlled option
Block names
Description
Factory default setting
Time range
Block type
Timed/Demand
HLA Dly
High-level alarm delay 5
seconds
MM:SS
Timer
Both
MinRunT
Minimum pump run time
1 second
MM:SS
Timer
Demand
Pmp1Lead
Pump 1 as lead (duty) pump
Off
On/Off
Soft button
Both
Pmp2Lead
Pump 2 as lead (duty) pump
Off
On/Off
Soft button
Both
Step
Action
Illustration
1
• Press the "
" button repeatedly until the display does not change.
• To begin the configuration process, press the "ESC" button.
T
M
06
72
74
32
1
6
2
• Press the "
" button to select "Set Param".
• Then press the "OK" button.
Warning
Do not select "Stop". Doing so may erase the panel programming, which cannot be
restored without the use of an EEPROM card, which is not included with the panel.
If "Stop" is selected accidentally, a confirmation screen will appear. Select "No" and
press the "OK" button immediately.
TM
06
72
75
32
16