15 (16) • No: 90 072 01 Rev 1 2005.07
Wiring diagrams
NOTE
The overcurrent protection should be set to AUTO. The tripping current should be max. the rated
current of the pump. Note that the scales for direct online and star/delta are different. The Y/D over-
load relay should be set at phase current = 0,58 x line current. The Y/D time relay should be set at 3s.