Greystone DH100ACDCPA Installation And Maintenance Manual Download Page 3

INLET
TUBE
END
PLUG

AIR HOLES

ARROWS

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector inlet sampling tube:

A78-2047-00
Figure 5. Tube mounting configurations with
varying air flow direction:

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

INLET

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

INLET

TUBE

INLET

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

EXHAUST

TUBE

INLET

TUBE

DETECTOR

HOUSING

A.

B.

C.

D.

NOTE: Orientations C and D apply ONLY to metal sampling tubes.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

WARNING

In no case should more than 2 air inlet holes be cut off the
tube. There must be a minimum of 10 holes in the tube ex-
posed to the air stream.

[5.4.2] Installation For Ducts More Than 8
Feet  Wide

NOTE: To install inlet tubes in ducts more than 8 feet wide,

work must be performed inside the air duct. Sampling of
air in ducts wider than 8 feet is accomplished by using
the ST-10 inlet sampling tube. If the tube is shorter than
the width of the air duct, install the end plug into the inlet
tube as shown in Figure 4 and support the end opposite
the duct smoke detector.

Install the inlet tube as follows:
1. 
Drill a  

3

/

4

” inch hole in the duct directly opposite the hole

already drilled for the inlet tube. Make sure the hole is 1 to
2”below the inlet hole on the opposite side of the duct to
allow for moisture drainage.

2. Slide the inlet tube with the flange into the housing bush-

ing that meets the air flow first. Position the tube so that
the arrows point into the air flow. Secure the tube flange
to the housing bushing with two #6 self-tapping screws.

3. From inside the duct, couple the other sections of the in-

let tube to the section already installed using the 

1

/

2

-inch

conduit fittings supplied. Make sure that the holes on
both of the air inlet tubes are lined up and facing into the

A78-2045-00
[5.4] Sampling Tube Installation for Ducts Greater
Than 1

1

/

2

 Feet Wide

The sampling tube is identified by a series of air inlet holes
on the tube. A telescoping tube is included for ducts up to
18” in width. All other lengths must be purchased sepa-
rately. Order the correct length, as specified in Table 1, for
width of the duct where it will be installed. The exhaust tube
is molded onto the base of the duct housing, and the A2440-
00 Exhaust Tube Extension is available as an accessory in
those cases where the molded exhaust port does not ex-
tend at least 2 inches into the duct.

The inlet tube is always installed with the air inlet holes fac-
ing into the air flow. To assist proper installation, the tube’s
mounting flange is marked with arrows. Make sure the inlet
tube is mounted so that the arrows point into the air flow
(see Figure 4). Figure 5 shows the various combinations of
tube mounting configurations with respect to air flow. Mount-
ing the detector housing in a vertical orientation is accept-
able, provided that the air flows directly into the sampling
tube holes as indicated in Figure 4.

Table 1. Inlet tubes required for different duct
widths:

Outside Duct Width

Inlet  Tube  Required

1 to 2 ft.

ST-1.5

2 to 4 ft.

ST-3

4 to 8 ft.

ST-5

8 to 12 ft.

ST-10

[5.4.1] Installation For Ducts Greater Than 1

1

/

2

Feet But Less Than 8 Feet Wide

1.

If the tube is longer than the width of the air duct, drill a 

3

/

4

hole in the duct opposite the hole already cut for the inlet
tube. Make sure the hole is 1” to 2” below the inlet hole on
the opposite side of the duct to allow moisture drainage
away from the detector. 

If the tube is shorter than the width

of the air duct, install the end plug into the inlet tube as
shown in Figure 4. Sampling tubes over 3 ft. long must be
supported at the end opposite the duct detector.

2. Slide the tube into the housing bushing that meets the air

flow first. Position the tube so that the arrows point into
the air flow.

3. Secure the tube flange to the housing bushing with two

#6 self-tapping screws.

4. For tubes longer than the width of the air duct, the tube

should extend out of the opposite side of the duct. If there
are more than 2 holes in the section of the tube extending
out of the duct, select a different length using Table 1.
Otherwise, trim the end of the tube protruding through the
duct so that  1” to 2” of the tube extend outside the duct.
Plug this end with the end plug and tape closed any holes
in the protruding section of the tube. Be sure to seal the
duct where the tube protrudes.

D100-68-00

3

I56-1525-000

Summary of Contents for DH100ACDCPA

Page 1: ...el interface alarm initiation HVAC control and other auxiliary functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detec For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm oc curs A ...

Page 2: ...s of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these pa rameters If necessary use a velocity meter to check the air velocity in the duct 5 2 Drill The Mounting Holes Remove the paper backing from the mounting template sup plied Affix the template to the duct at the desired mounting location Make sure the templat...

Page 3: ...dth All other lengths must be purchased sepa rately Order the correct length as specified in Table 1 for width of the duct where it will be installed The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not ex tend at least 2 inches into the duct The inlet tube is always i...

Page 4: ...mation Replacement filters can be ordered from Sys tem Sensor 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 Exhaust tube intake tube filter P N F36 09 00 5 6 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used to connect smoke detec...

Page 5: ...filters should be replaced because only a high percentage of con tamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the fil ters In no case should the pressure differential fall below 0 03 inches of water 6 2 Standby Alarm And Sensitivity Tests 6 2 1 Standby And Trouble Sta...

Page 6: ...FORMATION FOR WIRING OF AUXILIARY DEVICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTO...

Page 7: ...ed with dirt replace them with new filters If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 7 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining ...

Page 8: ...cement 1 Disconnect wiring from the terminal block 2 Remove the two power board mounting screws 3 Pull gently on the board to remove it 4 To replace the board align the board mounting features holes and the interconnect terminals Push the board into place 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block Power Supply Voltage 20 29 VDC 24 VAC 50 60 Hz 120 VAC 50 60 H...

Reviews: