background image

D100-68-00       Revision Date: 12-06-99

1

I56-1525-000

DH100ACDCIA & DH100ACDCPA
Air Duct Smoke Detector

INSTALLATION AND MAINTENANCE

Before Installing

ULC standard CAN/ULC-S524-M91 “Standard For The Installa-
tion Of Fire Alarm Systems” should be referenced for Canadian
Installations information. For additional reference the System
Sensor 

Guide for Proper Use of Smoke Detectors in Duct Ap-

plications (I56-473), provides detailed information on detector
spacing, placement, zoning, wiring, and special applications.
Copies of this manual are available from System Sensor.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following CAN/ULC-S536-97 requirements. The
detector should be cleaned at least once a year.

Table of Contents

Page

[1] General Description

 1

[2] Limitations of Duct Smoke Detectors

1

[3] Exploded View of Duct Smoke Detector Components 2
[4] Contents of the Duct Smoke Detector Kit

2

[5] Installation Sequence

2

[6] Duct Smoke Detector Maintenance and Test Procedures5
[7] Detector Cleaning Procedures

7

[8] Board Replacement

8

[9] Specifications

8

[10] Warranty

8

[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.

Model DH100ACDCA Air Duct Smoke Detectors are sup-
plied as an ionization model or photoelectronic model.
These two smoke detection methods are combined with an
efficient housing design that samples air passing through a
duct and allows detection of a developing hazardous condi-
tion. When sufficient smoke is sensed, an alarm signal is
initiated at the fire control panel monitoring the detector, and
appropriate action can be taken to shut off fans, blowers,
change over air handling systems, etc. These actions can
facilitate the management of toxic smoke and fire gases
throughout the areas served by the duct system.

DH100ACDCA detectors are designed to operate on 24 VDC/
VAC, 120 VAC, or 240 VAC. Alarm and supervisory relay con-
tacts are available for control panel interface (alarm initiation),
HVAC control, and other auxiliary functions. Auxiliary relays
are also provided for fan shut down or signaling of up to 9 other
detectors in the loop for multiple fan shut down. These detec-

For testing, the alarm can be enabled by a magnet activated
test switch or by the optional remote test station. The duct
smoke detector latches into alarm state when an alarm oc-
curs. A green LED flashes to indicate power, a red LED
signals local alarm indication, and optional accessories
offer a variety of annunciation capabilities. The
DH100ACDCA can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel, or
remote reset accessory.

[2] Limitations Of Duct Smoke Detectors

WARNING

The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUB-
STITUTE FOR OPEN AREA DETECTOR PROTECTION as
a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends
that the user read NFPA Standards 90A, 72, and 101. The
DH100ACDCA Air Duct Smoke Detectors are listed per UL 268A
& CAN/ULC-S529

WARNING

This device will not operate without electrical power.
Fire situations may cause an interruption of power. The sys-
tem safeguards should be discussed with your local fire pro-
tection specialist.

WARNING

This device will not sense smoke unless the ventilation sys-
tem is operating and the cover is installed.

WARNING

For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and op-
erated within ALL electrical and environmental specifica-
tions listed in this manual. Failure to comply with these
requirements may prevent the detector from activating when
smoke is present in the air duct.

[4] Contents Of The Duct Smoke Detector Kit
1. 
Complete housing base and cover assembly
2. Two #10 machine screws for mounting
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sam-

pling tube and optional exhaust tube extension

8. Two jack nuts

150 English Drive, Moncton, NB, E1E 4G7  CANADA

tel: 506-853-3057  fax: 506-853-6014

e-mail: [email protected]

www.greystoneenergy.com

tors are not designed for 2-wire applications.

Summary of Contents for DH100ACDCPA

Page 1: ...el interface alarm initiation HVAC control and other auxiliary functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detec For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm oc curs A ...

Page 2: ...s of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these pa rameters If necessary use a velocity meter to check the air velocity in the duct 5 2 Drill The Mounting Holes Remove the paper backing from the mounting template sup plied Affix the template to the duct at the desired mounting location Make sure the templat...

Page 3: ...dth All other lengths must be purchased sepa rately Order the correct length as specified in Table 1 for width of the duct where it will be installed The exhaust tube is molded onto the base of the duct housing and the A2440 00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not ex tend at least 2 inches into the duct The inlet tube is always i...

Page 4: ...mation Replacement filters can be ordered from Sys tem Sensor 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 Exhaust tube intake tube filter P N F36 09 00 5 6 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used to connect smoke detec...

Page 5: ...filters should be replaced because only a high percentage of con tamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the fil ters In no case should the pressure differential fall below 0 03 inches of water 6 2 Standby Alarm And Sensitivity Tests 6 2 1 Standby And Trouble Sta...

Page 6: ...FORMATION FOR WIRING OF AUXILIARY DEVICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTO...

Page 7: ...ed with dirt replace them with new filters If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 7 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining ...

Page 8: ...cement 1 Disconnect wiring from the terminal block 2 Remove the two power board mounting screws 3 Pull gently on the board to remove it 4 To replace the board align the board mounting features holes and the interconnect terminals Push the board into place 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block Power Supply Voltage 20 29 VDC 24 VAC 50 60 Hz 120 VAC 50 60 H...

Reviews: