INTRODUCTION

The single point, all purpose duct/immersion temperature transmitter utilizes a precision 

sensor that is encapsulated in 6 mm (0.236”) OD, 304 series stainless steel probe and is available 

in various lengths. All probes provide excellent heat transfer, fast response, and resistance to 

moisture penetration. A transmitter that provides a high accuracy signal with excellent long 

term stability, low hysteresis, and fast response. It is available with various ranges. A compact 

polycarbonate enclosure with a hinged and gasketed cover is provided for ease of installation. 

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the temperature 

transmitter. Failure to follow these instructions may result in product damage. Do not 

use in an explosive or hazardous environment, with combustible or flammable gases, as 

a safety or emergency stop device or in any other application where failure of the product 

could result in personal injury. 

Do not exceed the device ratings

.

MOUNTING (DUCT)

The temperature transmitter installs directly into any air duct with several lengths 

available for a wide range of duct widths/diameters. Select a suitable installation area in 

the middle of the duct wall.  To achieve the best reading, do not place in an area where 

air stratification may be present.  Mount the sensor at least 1.5 m (5 ‘) in either direction 

from elbows, dampers, filters or other duct restrictions.  Avoid areas where the sensor is 

exposed to vibrations or rapid temperature changes.

Once a suitable spot is selected, drill a 9.5 - 12 mm (3/8” - 1/2“) hole for the probe.

Slide the probe in the drilled hole until the enclosure is flush against the duct.  The airflow 

direction is not important.  Secure the enclosure to the duct with two #10 x 25 mm (1”) 

self tapping screws (not provided).  Tighten screws until the enclosure is tight against the 

duct and there is no movement of the enclosure as shown in Figure 1.  

A foam gasket on the back of the enclosure provides a tight seal against any air leaks. 

MOUNTING (IMMERSION)

The temperature sensor must be installed into a thermowell. 

Failure to use a 

thermowell will create leaks and could damage the sensor.  Install the thermowell as 

recommended in Figure 2.  For complete thermowell installation instructions, please 

refer to installation instructions provided with the thermowell. 

It is recommended to use heat conductive compound. Prior to installing the sensor 

inject a liberal amount into the thermowell and/or on the tip of the sensor.  Slide the 

probe into the thermowell until it makes contact with the bottom of the thermowell.  

Tighten set screw to secure probe in thermowell. See Figure 3.

The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on 

the latch on the right side of the enclosure, at the same time pulling on the cover, as 

illustrated in Figure 4.

A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. 

Screw the EMT connector or cable gland connector in until tight. See Figure 5. It is 

recommended that weatherproof conduit or cable gland fittings be used. The F style 

enclosure includes 1/2" NPT to M16 thread adapter and cable gland fitting.
Make wiring connections as per the “Wiring” illustrations on Page 2.

Swing door closed until securely latched. For added security, 2 screws are provided that 

may be installed in the integrated screw tabs. See Figure 6.

Recommended thermowell placement

Figure 3

Figure 4

Figure 5

Figure 6

Figure 2

Figure 1

Set Screw

EMT Connector

Thread adapter and 

cable gland fitting

IN-GE-TDAPXXX-01 07/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

All Purpose Temperature

Transmitter with LCD 

TDAP Series - Installation Instructions