background image

Page  3

CONFIGURATION

The transmitter is configured with switches located on the circuit board as shown on the PCB drawing. 

These switches are used to select the output signal type and the input pressure range. The unit is factory 

configured to operate in the 4-20 mA output mode. This can be changed to the voltage mode by moving 

the switch from the position marked 4-20 mA to the position marked Voltage. Once the output mode 

is changed to voltage, the output scale may be changed to either 0-5 Vdc or 0-10 Vdc. This is done by 

moving the switch to the 5V or 10V position marked 5/10 on the five position DIP switch. The pressure 

range is set with a five position DIP switch. 

Switch Setting LP-00

LP-01

LP-02

LP-03

LP-04

LP-05

LOW

1" WC

3" WC

6" WC

10" WC

0.25" kPa

0.5 kPa

MID

2" WC

5" WC

10" WC

15" WC

0.5" WC

1 kPa

HIGH

4" WC

8" WC

12" WC

20" WC

1 kPa

2 kPa

For example, if the LOW range is selected on the LPS-00 model, the pressure range will be 0-1” wc. If the 

4th DIP switch labeled (+/-) is also set to ON, then the pressure range will be –1 to +1” wc. This means 

that each model has six pressure ranges. For the LPS-00 they will be 0-1, 0-2, 0-4, ± 1, ± 2 and ± 4 “wc. Set 

LOW, MID or HIGH DIP switch to ON to select desired range.  Note: If no range is selected LCD will display 

"Err" indicating no range selected.

PNEUMATIC CONNECTIONS

The two pressure ports on the end of the enclosure are labeled High and Low. The output signal reads a 

positive value when the port pressure is higher on the High port than the Low port so ensure these ports 

are connected correctly. Use 0.170” I.D. flexible tubing for the pressure connections. Arrange the tubing 

to minimize stress on the connections and ensure there are no kinks in the tubing. For most accurate 

measurements, do not leave the Low port open to the atmosphere, run a return line from the Low port 

to the vicinity of the point being measured. 

Ensure the tubing to be used is clean and do not allow material to fall into the pressure ports as 

contamination could damage the sensor. When removing tubing use care to avoid breaking the ports. In 

some cases it is better to cut the tubing off rather than pulling it off but be careful not to cut the fitting or 

an air leak may occur. 

POWER UP INSTRUCTION

Before turning on the power, verify all wiring to ensure that it complies with one of the included wiring 

diagrams and verify that the output signal type is correctly selected with the switches. Also, review the 

specifications to ensure the power supply is correct and that the pressure is within the correct range. 

At this time, also inspect the internal pressure tubing that connects the sensor to the external ports to 

ensure that the tubing did not get kinked during shipping or installation.

Proper operation can be verified by measuring the output signal. For voltage output configuration, 

measure the voltage between the OUT and COM terminals. The voltmeter should read between 0-5 

Vdc or 0-10 Vdc depending on the output range selected. For current output configuration, insert a mA 

meter in series with the OUT terminal. The mA meter should read between 4 and 20 mA.

OPERATION

If the unit is set to a unipolar range such as 0-2” wc, then the pressure applied to the High port must be 

higher than the pressure applied to the Low port. In this case, if the Low port is left open to ambient 

pressure and the High port is used to measure a positive pressure, then the output pressure can be 

calculated as follows:

 

4-20 mA 

Pressure = [(Output current - 4 mA) / 16 mA] x Range

 

0-5 Vdc 

Pressure = (Output voltage / 5 V) x Range

 

0-10 Vdc 

Pressure = (Output voltage / 10 V) x Range

In the case of 0-2” wc, 4 mA or 0 V = 0” wc and 20 mA or 5 V or 10 V = 2” wc. Since the transmitter is linear, 

1” wc would be 12 mA or 2.5 V or 5 V. If the positive pressure connection is reversed then the transmitter 

will always output 4 mA or 0 V.

If the unit is set to a bipolar range such as ± 2” wc, then the pressure applied to the High port should be 

higher than the pressure applied to the Low port for a positive output response. In this case, differential 

pressure can be measured using both ports. If the High port has a positive pressure with respect to 

the Low port, then the output indicates a positive pressure. Negative pressure is indicated if the High 

pressure is less than the Low pressure. For bipolar ranges, the output pressure can be calculated as 

IN-GE-LPXXXS-02

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Summary of Contents for LP-S

Page 1: ...ace around the unit to connect the pressure tubing without kinking and to make the electrical connections avoid locations with severe vibrations or excessive moisture Drill a hole in the duct and insert so the probe point is facing into the air flow The enclosure has a standard opening for a 1 2 conduit and may be installed with either conduit and a conduit coupler or a cable gland type fitting Se...

Page 2: ...signal is available on the OUT terminal This signal is switch selectable for either a voltage output or a standard loop powered 4 20 mA output signal type When voltage mode is selected either 0 5 Vdc or 0 10 Vdc can also be selected These options are clearly indicated on the device circuit board The analog output signal is typically connected directly to the Building Automation System B A S and us...

Page 3: ...ng it off but be careful not to cut the fitting or an air leak may occur POWER UP INSTRUCTION Before turning on the power verify all wiring to ensure that it complies with one of the included wiring diagrams and verify that the output signal type is correctly selected with the switches Also review the specifications to ensure the power supply is correct and that the pressure is within the correct ...

Page 4: ... Thermal Effects 3 over compensated range Compensated Range 0 to 50 C 32 to 122 F Proof Pressure 40 W C 100 for 10 20 models Burst Pressure 60 W C 200 for 10 20 models Operating Conditions 0 to 50 C 32 to 122 F 5 to 95 RH non condensing Power Supply 20 28 Vac dc non isolated half wave rectified Supply Current 4 mA for voltage output 20 mA max for current output Input Voltage Effect Negligible over...

Page 5: ...D IN CANADA 116 5 mm 4 58 99 7 mm 3 93 0 5 NPT 96 27 mm 3 79 49 27 mm 1 94 112 5 mm 4 43 53 7 mm 2 11 IN GE LPXXXS 02 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: