This is useful in several ways, for example, discreet resistor may be connected to the W (min) and R 

(wiper) terminals of the FAILSAFE connector to set a minimum resistance value on power failure. If the 

signal interface is controlling a damper actuator, then the resistance would set a minimum open position 

on power failure.

To failsafe to the minimum signal interface resistance value, connect a wire jumper between the W and R 

terminals of the FAILSAFE connector.

To failsafe the maximum signal interface resistance value, connect a wire jumper between the B and R 

terminals of the FAILSAFE connector.

A manual potentiometer may also be connected to the FAILSAFE connector to allow manual control. 

The PCB has a MAN / AUTO jumper that can be used to force the failsafe mode. For normal operation the 

jumper is placed in the AUTO position. To test the system, place the jumper in the MAN position and the 

OUTPUT terminals will immediately connect to the FAILSAFE terminals so an external pot can be used to 

manually control the device connected to the signal interface output.

Return the jumper to the AUTO position for normal operation.

SPECIFICATIONS

POWER OUTPUT

Regulated Power Output ............ 20 Vdc ± 10% (use to power an external sensor)

Power Output Drive ...................... 30 mA maximum

INPUT SIGNAL

Voltage Range ................................ 0-5, 0-10, 0-15, 1-5, 2-10, or 3-15 Vdc (switch selectable)

Voltage Impedance ...................... >10 KΩ

Current Range................................. 0-20 or 4-20 mA (switch selectable)

Current Impedance ....................... 250 Ω

OUTPUT SIGNAL

Signal Type ....................................... Simulated potentiometer resistance (3 wire)

Resolution ........................................ 256 steps (no wrap around)

Resistance Accuracy ..................... ±5%

Standard Values ............................. 0-135 Ω, 4.5 watts

 

0-270 Ω, 3.0 watts

 

0-500 Ω, 3.0 watts

 

0-1000 Ω, 1.0 watts

 

other ranges available

GENERAL

Power Supply .................................. 23 to 30 Vdc, 22 to 27 Vac (half-wave rectified)

Consumption .................................. 110 mA maximum

Input Voltage Effect ...................... Negligible over specified operating range

Protection Circuitry ....................... Reverse voltage protected, overvoltage protected

Operating Conditions .................. 0 to 50°C (32 to 122°F), 5 to 95 %RH non-condensing

Storage Conditions ....................... -30 to 70°C (-22 to 158°F), 5 to 95 %RH non-condensing

Wiring Connections ...................... Screw terminal block (12 to 22 AWG)

Enclosure .......................................... Snap track mounting standard

 

117mm L x 83mm W (4.6" x 3.25")

Weight ............................................... 131gm (4.6oz)

Country of Origin ..............................Canada

DIMENSIONS

POWER

OFF   ON

S1

S2

S3

S4

INPUT SELECTION

MAN   AUTO

PWR  COM    20V     IN

W=MIN   B=MAX W    R    B

W    R     B

FAILSAFE

OUTPUT

117mm

4.6"

83mm

3.25"

Summary of Contents for GT-ARES Series

Page 1: ... configured with an offset resistance such as 20 30K Ω BEFORE INSTALLATION Read these instructions carefully before installing and commissioning the signal interface Failure to follow these instructions may result in product damage Do not use in an explosive or hazardous environment with combustible or flammable gases as a safety or emergency stop device or in any other application where failure o...

Page 2: ...eferenced ti the COM terminal Ensure the INPUT SELECT switches are set for the correct signal type either voltage or current The input signal will typically come from a DDC or BAS analog output WIRING POWER OUTPUT The 20V terminal is a regulated power supply output which provides a 20 Vdc power supply at 30 mA maximum that can be used to operate an external sensor WIRING RESISTANCE OUTPUT The sign...

Page 3: ...t wrap around In the above example with 0 5 Vdc input signal the W R resistance will increase to 135 Ω and will stay at 135 Ω even in 6 Vdc is applied to the input Voltage input signals are referenced to the COM terminal and have an input impedance of 10 KΩ Current input signals are also referenced to COM and have an input impedance of 250 Ω The current input is a sinking type signal the controlle...

Page 4: ...be used to manually control the device connected to the signal interface output Return the jumper to the AUTO position for normal operation SPECIFICATIONS POWER OUTPUT Regulated Power Output 20 Vdc 10 use to power an external sensor Power Output Drive 30 mA maximum INPUT SIGNAL Voltage Range 0 5 0 10 0 15 1 5 2 10 or 3 15 Vdc switch selectable Voltage Impedance 10 KΩ Current Range 0 20 or 4 20 mA ...

Reviews: