background image

ALARM TEST 

OPTIONS

TEST METHOD

DETECTOR RESET

Test/Reset 
Button

Press and hold test/reset button 
for at least 7 seconds

Press and release the 
test/reset button

Magnet Test 
(M02-04-00)

Place magnet on sensor cover in 
designated location for 5 seconds

Press and release the 
test/reset button

Remote Test 
Accessory

Red LED on sensor and acces-
sory will latch on: verify control 
panel alarm status and execu-
tion of all intended auxiliary 
functions (i.e. fan shutdown, 
damper control, etc.)

Reset at accessory, at 
system control panel, 
quick press and release 
the test/reset button

Smoke Test 
Port

1. Put detector into Speed-Up 
Test mode

Press and release the 
test/reset button

a. Press and hold Test/Reset but-
ton for 2 to 7 seconds

b. When in Speed-Up Test mode 
sensor LEDs will alternately 
flash Red and Green

2.  Lift tethered plug sealing the 
smoke test port via pull tab

3.  Spray canned smoke into the 
test port

4.  After test complete, tethered 
plug MUST be reinserted

TABLE 2.

FIGURE 7. MULTIPLE FAN SHUTDOWN 

(INTERCONNECTION OF DSD240’S):

DETECTOR 1

240 VAC

DSD240

DSD240

C, AUX A

NC, AUX A

30

DET.   

MAX.

INT/AUX–

INT+

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

DETECTOR 2

240 VAC

C, AUX A

NC, AUX A

INT/AUX–

INT+

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

[9] DETECTOR STATUS INDICATION

Detector Status is indicated by the sensor LEDs. Refer to Table 3 on page 7 for 
more details.

Note: The power board contains a diagnostic status indicator LED. However, 
this LED is not visible under normal operating circumstances.

[10] INTERCONNECTION (MULTIPLE FAN SHUT DOWN)

When using the interconnect feature, an alarm from an initiating device will 
switch the Aux Relays on the other devices interconnected.

[10.1] IMPORTANT INTERCONNECTION NOTES:

•  When using the interconnect feature, all interconnected units must be 

powered using the same independent supply.

•   Polarity must be maintained throughout the interconnect wiring. Connect 

the INT+ terminal on unit 1 to the INT+ terminal on unit 2 and so on. 
Similarly, connect the INT/AUX- terminal on unit 1 to the INT/AUX- ter-
minal on unit 2 and so on.

•  Up to 30 DSD240 units may be interconnected.

NOTE: Alarm can be reset only at the initiating device and not at the devices 
interconnected.

[11] VERIFICATION OF OPERATION

[11.1] POWERING THE UNIT

Apply 24 VDC power to 9 and 10 terminals on the power board or apply 240 
VAC on terminals named 240VAC. See Figure 7 and electrical specifications for 
details.

[11.2] PERFORM DETECTOR CHECK

VERIFY STANDBY AND TROUBLE TEST per 

Table 3

 on page 7. The use of a 

remote accessory for visible indication of power and alarm is recommended.

[11.3] SENSITIVITY VERIFICATION

The sensitivity of the sensor is confirmed to be operating within its allowable 
range each time the sensor LEDs blink green every 5 seconds. Note in a main-
tenance condition, the sensor LEDs will blink red every 5 seconds as depicted 
in 

Table 3 

on page 7. The maintenance condition indicates that the sensor is 

operating outside its original factory preset sensitivity and shall be cleaned or 
replaced. Replacement 2D51 sensors are available as a separate item. See Sec-
tion 9 for reference. This is a valid UL test.

[11.4] DETECTOR TESTING AND MAINTENANCE PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service. Disable the 
zone or system undergoing maintenance to prevent unwanted alarms and pos-
sible dispatch of the fire department.

[11.4.1] SMOKE RESPONSE TESTS

Option 1: Utilize smoke test port as described in 

Table 2

.

Option 2: To determine if smoke is capable of entering the sensing chamber, 
visually identify any obstructions. Plug the exhaust and sampling tube holes 
to prevent ducted air from carrying smoke away from the detector head, then 
blow smoke such as cotton wick, or punk directly at the head to cause an alarm. 
REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR 
WILL NOT FUNCTION PROPERLY.

H0639-01GS

[11.4.2] SMOKE ENTRY USING AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described in Section 7.1.

Drill a 

1

/

4

 inch hole 3 feet upstream from the duct smoke detector. With the air 

handler on, measure the air velocity with an anemometer. Air speed must be 
at least 100 FPM. Spray aerosol smoke* into the duct through the 

1

/

4

 inch hole 

for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 
duct smoke detector alarms, air is flowing through the detector. Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 

chamber and reset the duct smoke detector. Use duct tape to seal the aerosol 

smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries at home-

safeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector 

Tester model CHEK02 and CHEK06 available from SDi.  When used properly, 

the canned smoke agent will cause the smoke detector to go into alarm.  Re-

fer to the manufacturer’s published instructions for proper use of the canned 

smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 

manufacturer.  Misuse or overuse to these products may have long term ad-

verse effects on the smoke detector.  Consult the canned smoke agent manufac-

turer’s published instructions for any further warnings or caution statements.

[11.5] INSTALL THE COVER

Install the covers making sure that the cover fits into the base groove. Tighten 

the seven screws that are captured in the covers.

[11.6] DUCT CLEARING 

After an ALARM event occurs, the unit may be reset by pressing the RESET 

pushbutton. If the duct is not clear of smoke, the AUX relay will open for 20 

seconds, to allow the fans to run and clear the duct of smoke. If the smoke 

has cleared the unit will go into STANDBY, otherwise the unit will remain in 

ALARM.

IN-GE-DSD240-01-01 5 

I56-9200-001 

 

 5/6/2019

Summary of Contents for DSD240

Page 1: ...l Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC resistive 10A 250 VAC resistive 1 2 HP 240 VAC 1 4 HP 120 VAC NOTE Alarm auxiliary contac...

Page 2: ...hese parameters If necessary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop heat...

Page 3: ...y holes in the protruding sec tion of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct...

Page 4: ...ODEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FLUKE MODEL 87 OR EQUIVALENT FIGURE 5 PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM H0163 01 FIGURE 6 SYSTEM WIRING DIAGRAM FOR 4 WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUT...

Page 5: ...y 5 seconds as depicted in Table 3 on page 7 The maintenance condition indicates that the sensor is operating outside its original factory preset sensitivity and shall be cleaned or replaced Replacement 2D51 sensors are available as a separate item See Sec tion 9 for reference This is a valid UL test 11 4 DETECTOR TESTING AND MAINTENANCE PROCEDURES Notify the proper authorities that the smoke dete...

Page 6: ...and then gently pushing it until it locks into place 8 Reinstall the detector FIGURE 9 DETECTOR SENSOR EXPLODED VIEW SENSOR COVER SENSING CHAMBER COVER AND SCREEN SENSOR CHAMBER COVER REMOVAL TABS C1009 00 12 2 REINSTALLATION 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check Section 11 2 4 Notify the proper authorities testing has been completed and the smoke ...

Page 7: ...ern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 ar...

Page 8: ...send defective units post age prepaid to 150 English Drive Moncton N B Canada E1E 4G7 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreason able use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for an...

Reviews: