Page 31
OCF 6.1 Open Channel Flow Monitor
C
- sensor cable connections reversed
C
- through sensor cable
- use properly
grounded
metal conduit
C
- sensor cable extended and junction
not insulated
- Use metal Junction Box
C
- through enclosure
- use metal enclosure
C
- through 4-20mA output cable
- use shielded twisted pair (shielded to AC
ground)
- use grounded metal conduit
C
- wiring or installation close to variable
speed drive or inverter
- follow V.S.D. manufacturer’s instructions for
Drive grounding, wiring and shielding
Unit Receives No Return Echo Due To:
C,F,E
- foam on liquid surface
- use stilling well (open channel flow)
B
- target beyond
Max Range
- recalibrate
F
- sensor damaged
- remove sensor from mounting and aim at a
flat, stable target to test
F
- sensor misalignment
- check with a level
Wiring Problems Due To Sensor Cable:
A,C,F,
- open circuit
- check connections/continuity (8850 to 12700
ohms max./-30°C to +70°C )
B,F
- short circuit
- check connections/continuity (8850 ohms
min.)
F
- too long (max 500 ft., 150 m)
C
- bundled/run in conduit with power
cable
C
- sensor ground shorted to
conduit/enclosure
- insulate
A
- extended with wrong type of wire
- use RG62A/U coaxial only
C
- close to high voltage/large motors
C
- AC chassis/ground missing on
instrument power connections
Non-Linearity Due To: