Specification
Measuring range:
please refer to type plate
GTMU
– IF1
(standard):
-30,0 ... +100,0 °C
GTMU
– IF2
(standard):
-30,0 ... +100,0 °C
GTMU
– IF3
(standard):
-70,0 ... +400,0 °C
Optional meas. ranges:
max. -200,0 ... +500,0°C
Measuring probe:
internal Pt1000-sensor
Accuracy:
(at nominal temperature) ±0,2% of meas. value ±0,2°C (GTMU-IF1, GTMU-IF2)
±0,3% of meas. value ±0,2°C (GTMU-IF3)
Internal resolution:
0,025 °C
Adjusting:
via interface (with programming tool) by entering offset and scale.
Output signal:
4
– 20 mA (2-wire)
Auxiliary energy:
(supply voltage)
Uv = 10 ... 30 V DC
Permissible burden:
RA < (Uv
– 10 V) / 0.022 A [RA at Ohm, Uv at V]
Transfer accuracy:
±0,2% of output value ±0,2% FS
Supply effects:
< ±0.01 % / V
Temperature effect:
< ±0.01 % / K
Scaling:
via interface (with programming tool) by entering values for 4mA and
20mA output.
recommended min. meas. range:
50 °C
Ambient conditions for electronic
(in sleeve)
:
Nominal temperature:
25°C
Operating temperature:
-25 to 70°C
During operation please take care, that even at higher temperatures at the
sensor tube ( >70°C) the allowable temperature range of the electronics,
placed in the sleeve, may not exceed!
Relative humidity:
0 to 100 %RH
Storage temperature:
-25 to 70°C
Housing:
stainless steel housing
Dimensions:
depending on sensor construction
Sleeve:
Ø 15 x 35 mm (without screwing)
Tube length FL:
100 mm or 50 mm or on customer requirement
Tube diameter D:
Ø 6 mm or on customer requirement (available Ø: 4, 5, 6 and 8 mm)
Collar tube length HL:
100 mm or on customer requirement
Thread:
G1/2“ or on customer requirement (available threads: M8x1, M10x1,
M14x1.5, G1/8“, G1/4“, G3/8“, G3/4“)
IP rating:
IP67
Electrical connection:
via 4-pin connection cable (2 x current loop, 2 x interface)
Cable length:
1m or on customer requirement
Cable assignment:
current loop:
+Ub = green,
-Ub = yellow
interface:
GND = brown,
Data = white
EMC:
The device corresponds to the essential protection ratings established in the Regulations of
the Council for the Approximation of Legislation for the member countries regarding
electromagnetic compatibility (2004/108/EG). In accordance with EN61326 +A1 +A2 (appendix A,
class B), additional errors: < 1% FS. The tube have to be protected sufficiently against ESD pulses,
if the device is used in areas with risk of ESD. When connecting long leads adequate measures
against voltage surges have to be taken.