Manual for connection and operation of the GIR230 Pt1000 / DIF and GIR230 NTC /DIF

          Page 1 of 14

Manual for connection and operation of

GIR 230 Pt1000 / DIF

GIR 230 NTC / DIF

Version 1.3

Summary of Contents for GIR 230 NTC / DIF

Page 1: ...E33 0 31 6C 02 Manual for connection and operation of the GIR230 Pt1000 DIF and GIR230 NTC DIF Page 1 of 14 Manual for connection and operation of GIR 230 Pt1000 DIF GIR 230 NTC DIF Version 1 3...

Page 2: ...relay outputs 5 3 4 2 Connection of output 3 NPN output switching to ground 5 4 CONFIGURATION OF THE DEVICE 6 4 1 Selecting an input signal type 6 4 2 Selection of the output function 7 5 SWITCHPOINT...

Page 3: ...he device must be switched off and must be marked against re starting in case of obvious malfunctions of the device which are e g visible damage the device is not working as prescribed after storage o...

Page 4: ...factory the GIR230 has been subjected to various inspection tests and is completely cali brated Before the GIR230 can be used it has to be configured for the customer s application Hint In order to av...

Page 5: ...switching outputs properly Please take care that you must not exceed the limits of the voltage and of the maximum current of the switching outputs not even for a short period of time Please take extr...

Page 6: ...the device switches to the lower limit vice versa 4 1 Selecting an input signal type Turn the device on and wait until it completed its built in segment test Press button 2 for 2 sec The display will...

Page 7: ...you have to configure the preferred states and delay time of the outputs and the switch and alarm points Depending on your output function setting it may be possible that one or more settings describ...

Page 8: ...ss button 1 when not already done The device will be displaying 1 on turn on point of output 1 Use button 2 and button 3 to set the desired value the device s output 1 should be turning on Press butto...

Page 9: ...points for the second switching function 2 on 2 off Configuring these settings like the first switching function After that the alarm outputs have to be configured When pressing button 1 the device w...

Page 10: ...stays above 50 C for the entered delay time or after it had been falling below 15 C and stays below 15 C for the entered delay time Please note that the alarm outputs are inverted This means that the...

Page 11: ...1 slope adjustment 1 100 Example The setting is 2 00 the slope has risen 2 00 slope 102 When measuring a value of 1000 without slope adjustment the device would display 1020 with slope adjustment of 1...

Page 12: ...s check probe and device configuration Err 7 System error The device features an integrated self diagnostic function which checks essential parts of the de vice permanently When detecting a failure er...

Page 13: ...ty 5A 230VAC resistive load NPN output NPN Open Collector breaking capacity 30mA max 28VDC Output functions 2 point 3 point 2 point with alarm 3 point with alarm min max alarm Switching points arbitra...

Page 14: ...E33 0 31 6C 02 Manual for connection and operation of the GIR230 Pt1000 DIF and GIR230 NTC DIF Page 14 of 14...